Expansion units for SecuriFire 2000
38 / 128
Mounting and installation, Technical Description, T 811 086 en e
6
Expansion units for SecuriFire 2000
6.1
B6-LXI2 SecuriLine unit
The B4-DAI2 can be fitted to the B6-BCB13 main control unit of the SCP2000 if required and serves to connect two addi-
tional SecuriLine eXtended loops with their associated detectors and modules.
The unit also has a LAN interface.
Further information about the B6-LXI2 can be found in the technical description T 811 067.
6.1.1
Interfaces
X1
Interface for the B6-BCB13 main control unit
X2
Connector plug for 2 addressable loops
X3
Connection plug for the LAN-Interface (RJ45)
Loop connector plug (X2)
Fig. 47 B6-LXI2 interfaces
Loop
Pin
Designation
Function
2
1
Not present
2
G4
Screen
3
C4
GND loop end
4
L4
+24 V loop end
5
Not present
6
G3
Screen
7
C3
GND loop beginning
8
L3
+24 V loop beginning
1
9
Not present
10
G2
Screen
11
C2
GND loop end
12
L2
+24 V loop end
13
Not present
14
G1
Screen
15
C1
GND loop beginning
16
L1
+24 V loop beginning
6.1.2
Technical data
Voltage supply:
via SecuriFire 2000 main control unit
Supply voltage:
VCC 1
+3,4 V ±2 %
VCC 2
+5,1 V ±2 %
loop voltage
+27 V ±5%
Power consumption:
ICC
approx. 35 mA
Ambient temperature:
-5°C to +50°C
Rel. air humidity:
5% to 95%, without condensation
6.1.3
Compatibility information
Compatible main control unit:
B6-BCB13
SecuriFire-Studio:
from release 1.2