Technical data
38 / 40
ASD 535, Mounting and installation, T 140 333 d en
5
Technical data
Type
ASD 535
Supply voltage range
10.5 to 30 (
UL/FM = 12.4 to 27
)
VDC
Max. power consumption, measured in
12 VDC operation
24 VDC operation
Typical
Fan speed level V and at
10.5 VDC
18 VDC
24 VDC
ASD 535-1
Idle/fault
approx. 575
approx. 340
approx. 260
mA
Alarm I
approx. 660
approx. 390
approx. 295
mA
ASD 535-2
Idle/fault
approx. 645
approx. 380
approx. 290
mA
Alarm I + II
approx. 745
approx. 450
approx. 350
mA
ASD 535-3
Idle/fault
approx. 575
approx. 340
approx. 260
mA
Alarm I
approx. 695
approx. 405
approx. 310
mA
ASD 535-4
Idle/fault
approx. 645
approx. 380
approx. 290
mA
Alarm I + II
approx. 820
approx. 490
approx. 385
mA
additionally with 1 RIM 35 units
approx. 15
approx. 10
approx. 7
mA
additionally with 2 RIM 35 units
approx. 30
approx. 20
approx. 14
mA
additionally with XLM 35 / SLM 35
approx. 20
approx. 10
approx. 5
mA
additionally with MCM 35
approx. 25
approx. 15
approx. 10
mA
additionally with SIM 35
approx. 20
approx. 10
approx. 5
mA
SMM 535 (not from ASD but rather from PC via USB connection)
max. 100
mA
Switch-on current peak
(caused by EMC protection elements on the ASD supply input)
approx. 5
A
for max. 1
ms
Sampling pipe length
see T 140 421
Sampling pipe Ø, typical (inner/outer)
Ø 20 / 25
mm
Max. number of sampling holes
see T 140 421
Sampling hole diameter
Ø 2 / 2.5 / 3 / 3.5 / 4 / 4.5 / 5 / 5.5 / 6 / 6.5 / 7
mm
Response range (smoke sensor sensitivity see Sec.
EN 54-20, class A, B, C
Protection type acc. to IEC 529 / EN 60529
54
IP
Ambient conditions acc. to IEC 721-3-3 / EN 60721-3-3
3K5 / 3Z1
class
•
Extended ambient conditions:
•
Detector housing temperature range
–30 – +60 (
UL max. +40
)
°C
•
Temperature range of detector housing to Australian Standard AS 1603.8
–30 – +55
°C
•
Sampling pipe temperature range
–30 – +60
°C
•
Temperature range of sampling pipe to Australian Standard AS 1603.8
–30 – +55
°C
•
Max. approved temperature fluctuation in detector housing and sampling pipe operation
20
°C
•
Max. permitted storage temperature of detector housing (without condensation)
–30 – +70
°C
•
Ambient pressure difference of detector housing to sampling pipe (sampling holes)
must be identical
•
Detector housing humidity ambient condition (transient without condensation)
95
% rel. hum.
•
Detector housing and sampling pipe humidity ambient condition (continuous)
70
% rel. hum.
Max. loading capacity relay contact
50 VDC (
UL max. 30
) / 1 A / 30 W
Max. loading capacity per open collector output (electrical strength 30 VDC)
100
mA
Plug-in terminals
2.5
mm²
Cable entry for cable Ø
Ø 5 – 12 (M20) / Ø 9 – 18 (M25)
mm
Sound pressure level for fan speed level I / II / III / IV / V
34 / 36 / 39 / 40 / 41 dB (A) / 1 m
Housing
material
ABS blend, UL 94-V0
colour
grey 280 70 05 / anthracite violet 300 20 05
RAL
Approvals
EN 54-20 / EN 54-27 / FM 3230-3250 / UL 268 / UL 268A / ULC-S529
Dimensions
ASD 535-x (W x H x D)
265 x 397 x 148
mm
Weight
ASD 535-x (incl. SSD 535-x)
3,555
g
Notices
Power consumption at maximum permitted voltage drop in the electrical installation (guideline value for calcu-
lating the conductor cross-Sec.).
May cause an immediate actuation of the protection circuit in power supplies with overload protection circuits
(primarily in devices with no emergency power supply and output current of < 1.5 A).
Lower or higher temperature ranges are possible after consulting with the manufacturer. The manufacturer
must be consulted if deployment is to be in the condensation range.