Commissioning
84 / 105
ASD 531, Technical description, T 140 416 en
7.7.2
Test triggerings
Notice about test triggerings
Fire incident control and remote alerting must be blocked or deactivated on the superordinate FACP.
Reset the ASD 531 between each check (preferably on the FACP, as a reset on the ASD does not reset the
FACP).
Measure
Indicator
Procedure / remarks
(1)
Test alarm
Turn rotary switch “
Mode
” to position
“
5
”
--
(2)
Press key “
Set/Res
”
three times
Alarm
LED is lit
•
ASD 531 triggers alarm
via relay or XLM to the
FACP
(3)
Turn rotary switch “
Mode
” to position
“
1
”
Alarm
LED is lit
(4)
Press key “
Set/Res
”
Alarm
LED is lit
•
Put ASD into operating state again
•
Alarm is
not
reset
reset from FACP
(5)
Test fault
Turn rotary switch “
Mode
” to position
“
3
”
--
(6)
Press key “
Set/Res
”
three times
Fault
LED is lit
•
ASD 531 triggers fault
via relay or XLM to the
FACP
(7)
Turn rotary switch “
Mode
” to position
“
1
”
Fault
LED is lit
(8)
Press key “
Set/Res
”
Fault
LED is lit
•
Put ASD into operating state again
•
Fault is
not
reset
reset from FACP
(9)
Test pre-signal
Turn rotary switch “
Mode
” to position
“
4
”
--
(10)
Press key “
Set/Res
”
three times
Alarm
LED flashes 2 Hz
•
ASD 531 triggers pre-signal
via relay or XLM to
the FACP
(11)
Turn rotary switch “
Mode
” to position
“
1
”
Alarm
LED flashes 2 Hz
(12)
Press key “
Set/Res
”
Alarm
LED flashes 2 Hz
•
Put ASD into operating state again
•
Pre-signal is
not
reset
reset from FACP
7.8
Commissioning protocol
The ASD 531 ships with a commissioning protocol (fold-out) included in the scope of delivery. All of the measurements and
tests carried out during commissioning and maintenance are to be entered on the protocol, which is then signed.
Notice
•
When performing maintenance work or after certain other events, conclusions can be drawn concerning the
commissioning state of the ASD 531 based on the commissioning protocol. The protocol also serves as a kind
of life history of the ASD 531.
•
The commissioning protocol is to be filled out conscientiously and fully and stored in the ASD 531. If required,
a copy can be made and stored in the system dossier.