SEC CELLYTE 6-12TLG Installation And Operating Instructions Manual Download Page 1

1

CELLYTE 6-12TLG

STATIONARY GEL BATTERIES

INSTALLATION and OPERATING

INSTRUCTIONS

NON-SPILLABLE by DOT

(Department of Transportation)

ICAO (International Commercial Airline Organization)

and IATA (International Airline Transport Assocaiation)

Supplied Worldwide by :

SEC Industrial Battery Company

Last Revised May 2011

Summary of Contents for CELLYTE 6-12TLG

Page 1: ...and OPERATING INSTRUCTIONS NON SPILLABLE by DOT Department of Transportation ICAO International Commercial Airline Organization and IATA International Airline Transport Assocaiation Supplied Worldwide...

Page 2: ...ompensation 6 6 3 Maximum Charge Current 7 4 0 STORAGE 4 6 4 Recharge 7 4 1 General 4 6 5 Equalization Charge 7 4 2 Short Term Storage 4 7 0 STORAGE 7 5 0 INSTALLATION PROCEDURES 4 5 1 Battery Locatio...

Page 3: ...release all the gases produced to the environment whereas valve regulated batteries re combine most of the gases internally releasing very little to the environment Compared to a flooded battery of e...

Page 4: ...across the string is very important for maximum battery life The difference between the maximum and minimum block temperature in a series string can be no more than 3 C Excessive temperature variation...

Page 5: ...ons carefully and review Section 2 4 thoroughly before working on the battery CAUTION Remove all rings and watches before installing the connectors on the batteries Ensure that all tools are insulated...

Page 6: ...ages may take some months to become uniform The initial or equalize charge voltage for the CELLYTE 6 12TLG Bloc batteries is 2 35 volts per cell at 20 C Calculate the initial charge voltage for your i...

Page 7: ...ion Frequent deep discharges Rapid recharge required Long delay in recharging the battery after a discharge Unevenly paralleled string balance Equalization should be performed on an as needed basis Th...

Page 8: ...e actual AH capacity can be compared to the rated AH capacity to determine percentage capacity This type of test is usually used as an acceptance test of the battery The service test is usually perfor...

Page 9: ...s Stop discharge 10 Stop the timer and remove the load from the battery 11 Recharge the battery using the existing charger or an external charger An equalize voltage may be used to reduce charge time...

Page 10: ...10 SEC BATTERY MAINTENANCE REGISTER Date Maintenance Description SEC SEC Industrial Battery Co Industrial Battery Co...

Page 11: ...880 SEC Website www secbattery com Email brian harper secbattery com SEC European Sales Office 42 rue de la Rochette 77000 Melum France Tel 33 675 590 692 SEC Website www secbattery com Email Christia...

Page 12: ...Float Voltage Float Voltage Cell Float Current Cell Temperature Float Charge Voltage Float Charge Voltage Float Charge Voltage Open Circuit Voltage Open Circuit Voltage Open Circuit Voltage Cell I D...

Reviews: