background image

 

11 

10. Technical Data 

 

Power supply:

 

DC 3V (1 sealed lithium-ion-battery (type: EVE CR17335)) 

Type of device: 

Type B 

Sensor-type: 

electrochemical 

Product life: 

10 years after production date   

Sensitivity adjustment: 

Complies EN 50291-1: 2010 + A1: 2012 Standard. 
30PPM without alarm before 120 minutes 
50PPM between 60 to 90 minutes 
100PPM between 10 to 40 minutes 
300PPM less than 3 minutes 

Standby current: 

<20μA (average) 

Alarm current: 

<25mA (average) 

Air humidity: 

 

-10 - 40 

, air humidity ~ 95%d 

Alarm Volume:

  

≥85dB at 100cm at 3,2 ± 0,5KHz pulsing alarm 

CO alarm mute: 

approx. 5 minutes 

Battery Charge: Warning - Silence 

approx. 9 hours 

 

 

11. Information to the re-built battery 

 

This CO alarm detector contains a non-replaceable and non-rechargeable lithium-ion-battery. This 
must be activated before commissioning (

see chapter: "Installation"

). The battery will last 

approximately 10 years during normal operation. If the unit beeps twice every 30 seconds and the 
yellow LED (FAULT) flashes, the battery is empty and the CO alarm detector must be replaced as 
soon as possible. 

Note:

 Batteries should never be exposed to extreme heat (for example, by strong sunlight or fire). 

Never throw batteries into the fire. Risk of explosion! A constantly too high or too low air humidity 
may reduce the battery life.

 

 

 

Deactivation of the battery: 

This CO alarm detector is equipped with a battery monitoring circuit. When the battery becomes 
weaker, the alarm beeps twice every 30 seconds. The yellow LED (FAULT) flashes. This means 
that the CO alarm detector must be replaced. To stop the alarm sound and the flashing, the CO 
alarm detector should be deactivated. 

 

Deactivation of the CO alarm detector is final. The device can not be activated anymore after 

deactivated! 

 

After deactivation the CO alarm detector no longer detects CO-gas! 

Summary of Contents for GS810

Page 1: ...r should be installed 4 4 Product Overview 6 5 Installation 6 6 Startup 7 6 1 Activation of the CO alarm detector 7 6 2 Checking the function of the CO alarm detector 8 6 3 Recurring self test of the...

Page 2: ...alarm sounds This CO alarm detector may only be used in private rooms The CO alarm detector must be activated before use see chapter 6 1 After a maximum of 10 years as well as with signaling the batt...

Page 3: ...e following symptoms appear by a carbon monoxide poisoning The symptoms of carbon monoxide poisoning are similar to influenza but without fever Other symptoms are dizziness tiredness weakness headache...

Page 4: ...ple using a screwdriver pliers hammer etc Do not drop the device because this can damage it The conversion of this product is not allowed Any other use than the description may result in damage to the...

Page 5: ...entilators Do not install near ventilation systems chimneys or exhaust pipes as well as doors and windows as this may have a lower carbon monoxide concentration Keep the CO alarm detector away from st...

Page 6: ...mute 4 FAULT Error display yellow LED 5 POWER Control light green LED 5 Installation Before starting up this product please check for external damage In case of visible external damage we immediately...

Page 7: ...e screw until the screw head protrudes about ca 55mm from the wall 3 The mounting hole for the screw is located on the rear of the housing Insert the screw head into the mounting hole and press the CO...

Page 8: ...urring self test of the CO alarm detector When operating properly the green LED POWER flashes every 30 seconds Note If the CO alarm detector is not working properly contact the manufacturer 7 Explanat...

Page 9: ...flash every 30 seconds Warning of the end of life If the device beeps three times every 30 seconds and the yellow LED FAULT flashes the end of life of the device is reached CO alarm warning At a dange...

Page 10: ...have arrived The alarm must not be deactivated during this time 6 Do not restart the switched off combustion device until it has been checked by an expert 7 Check each combustion device If no special...

Page 11: ...chapter Installation The battery will last approximately 10 years during normal operation If the unit beeps twice every 30 seconds and the yellow LED FAULT flashes the battery is empty and the CO alar...

Page 12: ...free from contamination at all times in order to ensure proper functioning Note Never open the housing to clean the unit from the inside This can impair the functionality and the warranty guarantee wi...

Page 13: ...e harmful Substances which are contained in the batteries may cause danger to health and the environment in case of improper disposing 14 General Disposal This product may not be disposed of with hous...

Reviews: