Seametrics FT522 Instructions Download Page 1

FT522 Usage Monitor
Instructions

rev. b

LT-10829-A
Page 1 of 4

Specifications

Power

115 VAC (220 VAC optional),
50/60 Hz; 12 VDC

Temperature

32

°

 -130

°

 F (0

°

 - 55

°

 C)

Enclosure

Precision cast aluminum,
NEMA 4X

Alarm Outputs

Two Form C SPDT relay,
115 VAC 5A max

Max Pulse Output

100 mA at 60 VDC

Memory Type

Non-volatile EEPROM
auto-backup

Sensor Power

12 VDC, 10 mA

Totalizer

8 digit

Rate Display

5 digit

Volume Units

Gallons, cubic feet, cubic
meters, liters, million gallons

Time Units

Minutes, hours

Analog Output

4-20 mA, 0-5 VDC, 0-10 VDC,
opto-isolated

Sensor Input

Open collector current sink,
ESD protected

Max Input Frequency

1,000 Hz

Shipping Weight

7 lbs

General Information

The FT522 is a flowmeter monitor with added
output and alarm features. It is designed for use
with SeaMetrics flow meters and sensors, as well
as other units which have a pulse or frequency
output. It displays flow rate and total in large digits
on an easily-read backlit display. Units are user
selectable between gallons, cubic feet, and cubic
meters.

The primary output of this unit is a user-set alarm
relay which signals excessive total flow within a
given time period (up to 48 hours). This is typically
used to detect an elevated usage level in a cooling
tower  or potable water application. The dual relays
can be  connected to an alarm, autodialer, or any
other switch-controllable device.

In addition to the usage alarm, the FT522 has
analog output (4-20 mA, 0-5 VDC or 0-10 VDC)
and  programmable pulse output. These can be
used for data logging or to provide proportional
chemical feed,  using an externally-controlled
metering pump.

Features

Relay 1

Relay 2

Pulse

Output

0:00:00

0   GAL

ELAPSED

Set

Resume

Stop

Easy-read

backlit display

Remote control terminals

(inside housing)

Rugged cast aluminum

housing

(wall or panel mount)

Choice of

rate/volume units

Alarm output

indicator LED

Accessible

control

buttons

Summary of Contents for FT522

Page 1: ... a pulse or frequency output It displays flow rate and total in large digits on an easily read backlit display Units are user selectable between gallons cubic feet and cubic meters The primary output of this unit is a user set alarm relay which signals excessive total flow within a given time period up to 48 hours This is typically used to detect an elevated usage level in a cooling tower or potab...

Page 2: ...ive powered or passive unpowered output When using the 12 VDC powered input you may only select passive output Power Connection Connect AC or DC power as desired to the appropriate terminals For safety if using AC power be sure to connect the ground terminal provided to a good earth ground If using DC power be Settings Set Units Press Use to select volume units Use to select the particular unit de...

Page 3: ...metering pumps Main power fuse 250mA part 26926 Ribbon connector from display board Meter Power signal RED BLACK Dry contact Customer Supplies 1A Fuse WHITE Ground A B An Output A P Passive Active Jumpers 5V 10V 4 20mA PC1 power supply P N 05040 AUTODIALER Neut Hot Gnd 110 VAC Alarm 1 Alarm 2 ALARM Connections 3 of 4 the end of which the unit will alarm if total flow has exceeded its setting To se...

Page 4: ...or for information 5 50 gasket PANEL CUTOUT 5 50 6 03 6 03 1 4 holes 4 required Panel Cut out Dimension Caution Always disconnect power to the unit before opening the terminal cover Do not reconnect power until all connections have been made and the terminal cover has been replaced 20419 80th Ave So Kent WA 98032 USA Phone 253 872 0284 Fax 253 872 0285 www seametrics com 1 800 975 8153 4 of 4 ...