Seametrics FT520-86 Instructions Download Page 1

FT520-86 Flow Rate Alarm
Instructions

          rev b

LT-11298-A

Page 1 of 4

Specifications

Power

115 VAC (220 VAC optional),
50/60 Hz; 12 VDC

Temperature

32

°

 -130

°

 F (0

°

 - 55

°

 C)

Enclosure

Precision cast aluminum,
NEMA 4X

Alarm Outputs

Two Form C SPDT relay,
115 VAC 5A max

Max Pulse Output

100 mA at 60 VDC

Memory Type

Non-volatile EEPROM
auto-backup

Sensor Power

12 VDC, 10 mA

Totalizer

8 digit

Rate Display

5 digit

Volume Units

Gallons, cubic feet, cubic
meters, liters, million gallons

Time Units

Minutes, hours

Analog Output

4-20 mA, 0-5 VDC, 0-10 VDC,
opto-isolated

Sensor Input

Open collector current sink,
ESD protected

Max Input Frequency

1,000 Hz

Shipping Weight

7 lbs

General Information

The FT520 is a flowmeter monitor with added
output and alarm features. It is designed for use
with SeaMetrics flow meters and sensors, as well
as other units which have a pulse or frequency
output. It displays flow rate and total in large digits
on an easily-read backlit display. Units are user
selectable between gallons, cubic feet, and cubic
meters.

The primary output of this unit is is a set of user-
configurable alarm relays which can signal when a
maximum or minimum flow is reached.  Applica-
tions tyically include detection of a pipeline failure
or of a pump that has run dry.  The dual relays can
be connected to an alarm, auto dialer, or any other
switch-controllable device.

In addition to the flow rate alarm, the FT520 has
analog output (4-20 mA, 0-5 VDC or 0-10 VDC)
and  programmable pulse output. These can be
used for data logging or to provide proportional
chemical feed,  using an externally-controlled
metering pump.

Features

Relay 1

Relay 2

Pulse

Output

0.00 GPM

0.00  GAL

Set

Start

Stop

Resume

Easy-read

backlit display

Remote control terminals

(inside housing)

Rugged cast aluminum

housing

(wall or panel mount)

Choice of

rate/volume units

Alarm output

indicator LED

Accessible

control

buttons

Summary of Contents for FT520-86

Page 1: ...have a pulse or frequency output It displays flow rate and total in large digits on an easily read backlit display Units are user selectable between gallons cubic feet and cubic meters The primary output of this unit is is a set of user configurable alarm relays which can signal when a maximum or minimum flow is reached Applica tions tyically include detection of a pipeline failure or of a pump th...

Page 2: ...n using the 12 VDC powered input you may only select passive output Power Connection Connect AC or DC power as desired to the appropriate terminals For safety if using AC power be sure to connect the ground terminal provided to a good earth ground If using DC power be sure to use a Seametrics PC1 part number 05040 or comparable 12 V 500 mA power supply Replace the front panel taking care to reconn...

Page 3: ... fuse 250mA part 26926 Ribbon connector from display board Meter Power signal RED BLACK Dry contact Customer Supplies 1A Fuse WHITE Ground A B An Output A P Passive Active Jumpers 5V 10V 4 20mA PC1 power supply P N 05040 Neut Hot Gnd 110 VAC Alarm 1 Alarm 2 Autodialer Pump Alarm Valve Shutoff Analog Switch Analog Jumper Connections 3 of 4 Set 20 mA Out The SET 20mA RATE programs the flow rate at w...

Page 4: ...r for information 5 50 gasket PANEL CUTOUT 5 50 6 03 6 03 1 4 holes 4 required Panel Cut out Dimensions Caution Always disconnect power to the unit before opening the terminal cover Do not reconnect power until all connections have been made and the terminal cover has been replaced 20419 80th Ave So Kent WA 98032 USA Phone 253 872 0284 Fax 253 872 0285 www seametrics com 1 800 975 8153 4 of 4 ...

Reviews: