PN: 123-194, Rev. F
Page 22 of 44
III. System Status Indicator Light Installation
Select a location at the helm on or near the console that is in full view of the
helmsman. The location selected must have access for electrical wiring. Remove the
adhesive protective cover from back of indicator faceplate and attach. For proper
adhesion, surface must be clean and dry and temperature must be above 50°F (10°C).
Use the preformed faceplate hole as a template and carefully drill a 5/16 inch (8 mm)
hole. Insert indicator light wire (see Figure 7).
CAUTION:
PRIOR TO WIRING INDICATOR LIGHT, TURN OFF ELECTRICAL POWER BY SWITCHING
OFF CIRCUIT BREAKER, REMOVING FUSE OR DISCONNECTING POSITIVE BATTERY
TERMINAL. FAILURE TO DISCONNECT ELECTRICAL POWER WHILE MAKING
ELECTRICAL CONNECTION CAN RESULT IN INJURY FROM FIRE OR ELECTRICAL
BURNS.
The standard indicator light is rated for 12 VDC (contact factory for other voltages).
Wire in accordance with the American Boat and Yacht Council (ABYC), Standard E-9,
Direct Current Electrical System on Boats, copies of which may be obtained from ABYC,
Edgewater, MD, USA, 21037, +1 (410) 956-1050.
Supplies, which are not included with your Sea-Fire system and should be at hand
before the indicator light installation, are as follows:
1.
Five (5) ampere in-line fuse and holder.
2.
Sufficient length of insulated minimum 16 AWG stranded wire.
3.
Crimp on wire connectors.
4.
Crimp pliers, hand tools.
Attach one wire lead from the in-line fuse (C) to the ignition terminal on the starter
switch. Connect other lead from the in-line fuse to the indicator light (D). Connect
remaining indicator lead (E) to one of the Sea-Fire cylinder pressure switch connector
wires (F). Connect the remaining cylinder pressure switch lead (G) to common ground,
which may be the negative battery bus at the control panel, or directly to the engine
block (see Figure 7).
NOTE: The 12VDC + 24VDC bulbs do not have polarity. If installing LED light kits,
proper polarity must be maintained. The supervisory pressure switch does not have
polarity.
CAUTION:
ELECTRICAL SYSTEMS VARY FROM VESSEL TO VESSEL AND THESE DIRECTIONS MAY
NOT BE APPLICABLE FOR YOUR INSTALLATION. SHOULD YOU HAVE ANY DOUBTS
OF SAFELY ACCOMPLISHING THIS INSTALLATION, CONTACT A QUALIFIED MARINE
ELECTRICIAN OR SEA-FIRE MARINE USA AT (410) 687-5500 FOR TECHNICAL
ASSISTANCE.
Summary of Contents for FD 1001-1500
Page 27: ...PN 123 194 Rev F Page 27 of 44 Pressure Temperature Graphs for HFC 227ea nominal at 70 F ...
Page 33: ...PN 123 194 Rev F Page 33 of 44 ...
Page 34: ...PN 123 194 Rev F Page 34 of 44 ...
Page 35: ...PN 123 194 Rev F Page 35 of 44 ...
Page 36: ...PN 123 194 Rev F Page 36 of 44 ...
Page 37: ...PN 123 194 Rev F Page 37 of 44 ...
Page 38: ...PN 123 194 Rev F Page 38 of 44 ...
Page 39: ...PN 123 194 Rev F Page 39 of 44 ...
Page 40: ...PN 123 194 Rev F Page 40 of 44 ...
Page 41: ...PN 123 194 Rev F Page 41 of 44 ...
Page 42: ...PN 123 194 Rev F Page 42 of 44 ...