background image

olo

s

d

c o

ete

t r

t st

r

e e

s

®

Quick Start Guide to the

range of detector test equipment

 

 

Solo

Solo

 

330 Aerosol Dispenser

Solo

Solo

 

100 and 

 108 Telescopic Access Pole 

Solo

 

A4 

Smoke Detector 
Tester

Solo

 

C6 

CO Detector 
Tester

Solo

 

A7 

Detector 
Duster

3

4

Unscrew and remove 
retainer cup.

Place aerosol canister
into cup.

Replace retainer cup and
screw upwards. Adjust until
aerosol activates and unscrew
slightly. 

Insert the 

 330 into

 pole. Place 

 330

over the detector and press
upwards to activate the 
aerosol (1 second burst).

Solo

Solo

Solo

         If the detector has not 
         responded in 10 seconds, 
repeat the test every 10 seconds. 
Number of total sprays should 
not exceed 5. If the detector fails 
to activate, check equipment and 
retest. If the detector does not 
activate it will require further 
investigation.

 To prevent the possibility 

of the aerosol discharging while in 
transit, loosen the retainer cup by 
unscrewing 2 full turns.

TIP

Maintenance 

Excess liquid 

deposits may be experienced 
following extended periods of use. 
To clean, use a lint-free cloth. 
Wash the cup with a mild 
detergent in warm water and dry 
thoroughly.

Designed to be used only
with 

 330 (332)

dispenser.

Solo

IMPORTANT

Read the instructions and
warnings before use and 
dispose with care.

Designed for handheld use only. 
Use a 

 200 removal tool to 

remove and clean high-mounted
detectors.

Solo

IMPORTANT

Read the instructions and
warnings before use and 
dispose with care.

5

2

3

Twist to lock button.

 100: 4 sections
 108: 2 sections

Solo
Solo

Insert 

 tool into pole. 

Solo

Solo

 

100

Solo

 

101

Solo

 332 Aerosol dispenser

available for larger detectors.

1

2

1

Extend the 

 pole.

Solo

Solo

 

423/4 Heat Detector Tester

Solo

 

200 Universal Removal Tool

1

 

SAFETY INFORMATION

Attach power cable, secure
clip, and if required, add
optional extension cable.

Insert the tool into 
pole.

Solo

Connect to power and press

 switch. Place over

detector. 

ON

4

         If detector does not 
         activate within 1 minute
it may be faulty.

 423 (110v)
 424 (230v)

Fitted with a thermal cut-out
protection system.

Solo
Solo

DO NOT TOUCH
METAL GRID.

DO NOT BLOCK AIR
VENTS.

NO USER SERVICEABLE
PARTS.

Pull and twist the Tri-grips
to adjust for different
detector sizes.

When inserting into a 
pole, locate lower button for
access to detectors at angles.

Solo

When inserting into a 
pole, locate lower button for 
use vertically. 

Solo

Grip detector, twist and
pull down to remove. 

1

2

3

1

2

3

4

A

 101 1.1m extension pole

can extend the 

 100 and 108

telescopic pole, or may be used by itself
with the 

 range of tools.

 A maximum of 3 extension poles is 

recommended.

The Solo poles can be 

cleaned with mild detergent in warm 
water and a soft lint-free cloth. 
Lubrication is not necessary.

The use of Personal

1

Protection Equipment is recommended
when using tools at height.

 Solo

Solo

Solo

Tip

Maintenance 

Warning 

Solo

 

461 Cordless Heat Detector Tester

Solo

 

760 Battery Baton Charging

4

Insert a charged battery
baton into the tool and pole.

 Ensure correct

1

orientation when inserting
battery baton into tool and do
not use undue force to insert.

Caution

Press the red switch to turn
on. LED illuminates green.
Flash at slow rate indicates
normal STANDBY mode.

Position the latch and place
over detector.

 

         The tool will automatically start testing 
         when infra-red beam in cup is broken. 
The green LED will flash faster. Hold in place 
until the alarm is activated*. When the detector
alarms, remove the tool from the detector.

It will revert to standby mode (slow flashing 
green LED), and the internal blower will cool
the heating element for a few seconds. After 
testing, switch off at red switch to preserve 
battery baton life.

Connect charger to power
outlet or lighter socket in
vehicle using mains lead 
supplied or the umbilical DC 
connecting lead. Power LED 
will illuminate.

1

 Do not attempt

to use or charge the battery
baton if either the charger 
unit or the battery baton 
connection point are damaged.

Warning

Connect battery to charger. 
Fast Charge LED will illuminate.

When battery baton is fully 
charged, Fast Charge LED will
extinguish. Trickle charge LED 
will illuminate.

International power outlet cables are 
available from your supplier.

 Ideally, fully discharge battery baton 

in normal use before recharging.

Tip

(*If the detector fails to activate it may be faulty. Insert a 
replacement detector and test again)

Trickle charge

Fast charge

Trickle charge

Fast charge

1

2

3

1

<90min.

2

Tip

 Ensure the

detector rests
firmly on
platform.

 

1

Remove battery baton when not in use.

 Caution

2

Designed to be used only for
testing CO Detectors with 

Functional Speed-Up 
Test Feature
.

IMPORTANT

Read the instructions and
warnings before use and 
dispose of with care, even
when empty.

C6

CO

 Do not use on

1

any other type of CO detector,
or with any type of aerosol
dispenser.

Caution

Insert straw into the nozzle.
Apply the gas using the straw
to the entry port of the
detector. 

solo

detector

testers

TM

Summary of Contents for Solo Series

Page 1: ...riel de test de d tecteurs per l apparecchiatura della gamma per il colaudo dei rilevatori para la gama de equipos de comprobaci n de detectores Solo Solo Solo Solo ENGLISH DEUTSCH FRAN AIS ITALIANO...

Page 2: ...ector twist and pull down to remove 1 2 3 1 2 3 4 A 101 1 1m extension pole can extend the 100 and 108 telescopic pole or may be used by itself with the range of tools A maximum of 3 extension poles i...

Page 3: ...Netzspannung anschlie en einschalten gr ner Schalter und ber den Melder halten L st der Melder nicht innerhalb von 1 Minute aus ist er m glicherweise defekt In zwei Versionen erh ltlich Solo 423 110...

Page 4: ...ecteur et renouveler le test Disponible en version 120 V et 230 V Comprend un syst me de protection thermique NE PAS TOUCHER LA GRILLE EN METAL NE PAS OBSTRUER LES EVENTS LES PIECES NE SONT PAS REPARA...

Page 5: ...Prolunga opzionale Fissare il morsetto Inserire il 423 4 nel palo Premere l interruttore Posizionare sotto il Rilevatore Se il rilevatore non si attiva entro 1 minuto pu essere guasto Disponibile nell...

Page 6: ...Fije los contactos Introduzca el 423 4 en el tubo Pulse el interruptor de Encendido Coloque sobre el Detector Si el detector no se ha activado dentro de 1 minuto puede que est defectuoso Disponible e...

Page 7: ...ith 330 332 Dispensers Solo Canister for handheld use only for access remove detectors at height with 200 Solo Cordless Heat Tester inc 2 x 760 Battery Batons 1x 725 Battery Charger For testing detect...

Page 8: ...r warranty either express or implied or to form the basis of any legal relations between the parties hereto additional to or in lieu of such as may be applicable to a contract of sale or purchase Tel...