INSTALLATION INSTRUCTIONS EH SERIES
ELECTROMAGNETIC DOOR HOLDER
801 Avenida Acaso, Camarillo, Ca. 93012 • (805) 494-0622 •
www.sdcsecurity.com • E-mail: [email protected]
Any suggestions or comments to this instruction or
product are welcome. Please contact us through
our website or email [email protected]
P:\INSTALLATION INST\ACCESSORIES\INST-EH SERIES.vsd REV C 10-14 Page 1
ELECTRICAL
This product is a high quality electromagnetic holding device intended for use in fire door
applications, but can be used for other magnetic applications.
PLEASE READ INSTRUCTIONS CAREFULLY!
PERFORMANCE DATA
12 V
24 V
24 V
120 V
24 V
220 V
MODEL
1224
24120
24220
40
40
20
-
20
-
38
36
19
20
19
15
C & L
C & H
C & L
C & H
C & L
C & H
30
30
40
35
20
22
13.6
13.6
18.1
15.8
9.0
9.8
VOLTAGE
DC / mA
AC / mA TERMINALS
Lb.
Kg.
To obtain performance values in table above, apply high
listed voltage to low voltage terminals (C & L).
NOTE: This configuration can only be applied to Models
1224 & 24120.
#6-32 SCREW &
SEM PLATE
TO NEXT UNIT
SURFACE MOUNTING
GENERAL MOUNTING
MIS-ALIGNMENT
EHR1
EHRA4
8"
[203mm]
5"
[127mm]
EXTENSION:
TO CALCULATE EXTENSION LENGTH;
SUBTRACT 3" (117mm) FROM WALL TO
DOOR AT DESIRED ANGLE.
WALL
DOOR
EXAMPLE:
5" OVERALL DISTANCE
USE EHR2 (2" EXTENSION)
90
o
C
L
H
LOW VOLTAGE
HIGH VOLTAGE
POWER INPUT
C -COMMON
L – LOW VOLTAGE
H – HIGH VOLTAGE
HIGH HOLDING FORCE / SPECIAL APPLICATIONS:
24 V
120 V
MODEL
1224
24120
85
-
81
100
C & L
C & L
75
110
34.0
49.8
VOLTAGE
DC / mA
AC / mA TERMINALS
Lb.
Kg.