1511S Operational Description (NFPA-101)

The 1511S operation complies with the following building and fire codes:  NFPA 101; NFPA 1-UFC; UBC; IBC; IFC; SBC; 
California Building Code.  Listings: UL Listed: Special Locking Arrangements and Auxiliary Locks; California State Fire 
Marshal (CSFM) Listed.

The door is normally closed & secured and/or latched.  The model 1511S Exit Check secures the door in the locked 
condition, and the display shows the preset delay time.  

Activation of the 1511S Exit Check is made by releasing the door latch and applying up to 15 lbs. of pressure to the door, 
giving a pre-activation warning tone.  (A 1 or 2 second nuisance delay will prevent false activation of the alarm). 

When the nuisance delay time has been exceeded, the Exit Check begins the irreversible door release cycle.  At this 
time the display continues to count down, the verbal warning continues and an alarm output is provided to alert 
personnel of an unauthorized exit.

The integral digital countdown display and voice commands inform the person intending to exit of the seconds remaining 
to unlock. The Exit Check will release the door after the 15 or 30 second delay cycle has expired, allowing free egress.  A
steady warning tone with the voice command “Exit Now” will sound until the Exit Check is reset by authorized personnel. 

1511S Operational Description (BOCA/Chicago)

The 1511S operation complies with BOCA National Building Code and the Chicago Building Code:  UL Listed, Special 
Locking Arrangements and Auxiliary Locks.

The releasing operation of the 1511S is the same as described above, with the exception that the door relocks 
automatically 30 seconds after closure (

reset switch not required

).  Each time the door is open before 30 seconds has 

elapsed the relock timer resets and relocks the door in 30 seconds.

SECURITY DOOR CONTROLS

3580 Willow Lane, Westlake Village, CA 91361-4921  •   (805) 494-0622  •  Fax: (805) 494-8861
www.sdcsecurity.com  •  E-mail: [email protected]

P:\INSTALLATION INST\Delayed Egress\INST-1511ST\INST-1511ST.vsd      Rev E               09-08     Page 1

INSTALLATION INSTRUCTIONS

EXIT CHECK

®

DELAYED EGRESS EMLOCK

®

1511S / 1511T

 PUSH UNTIL ALARM

SOUNDS. DOOR CAN BE

OPENED IN 15 SECONDS.

Application

When unauthorized egress is initiated, the Exit Check

®

 delays egress through the door for 15 or 30 seconds.  

Meanwhile, the person exiting must wait while personnel or security respond. An integral digital countdown display and 
voice commands inform the person intending to exit of the  seconds remaining to unlock. The door unlocks after 15 or 
30 seconds have elapsed, permitting egress.  A signal from the fire/life safety system will release the lock for uninhibited 
egress in an emergency.

Exit Check

®

 applications include:

Restricting the egress of patients for their own safety.
Restricting the egress of commercial center patrons for security application needs.
Controlling pedestrian traffic in transportation facilities, including airport jetways and tarmacs

California Building 

Code Compliant

KEEP PUSHING. THIS DOOR 

WILL OPEN IN 15 SECONDS. 

ALARM WILL SOUND.

Summary of Contents for 1511S

Page 1: ...the Chicago Building Code UL Listed Special Locking Arrangements and Auxiliary Locks The releasing operation of the 1511S is the same as described above with the exception that the door relocks autom...

Page 2: ...and access or sustained bypass 101 PAM Visual audible annunciation timed access sustained bypass and audible mute SDC Annunciator Consoles provide remote annunciation of multiple openings Stations ar...

Page 3: ...ON TEMPLATE WITH REGARD TO SELECTING THE PROPER HOLE SIZE FOR ARMATURE MOUNTING BOLT 2 1 2 2 5 8 11 2 3 4 P INSTALLATION INST Delayed Egress INST 1511ST INST 1511ST vsd Rev E 09 08 Page 3 NOTES 10 sel...

Page 4: ...s over the socket head mounting screws using a soft hammer to avoid damage to the lock case ARMATURE MOUNTING INSTRUCTIONS Figure 2B HOLLOW METAL DOOR From sexnut side of door drill exactly 1 2 hole t...

Page 5: ...tors 8 or 10 conductors Power Supply To Fire Panel AC Mains 2 conductors PUSHUNTILALARM SOUNDS DOORCANBE OPENEDIN15SECONDS Key Switch or Access Control Optional L3 OPTION REMOVE J6 ONLY IF A FIRE PANE...

Page 6: ...OPTIONAL RED GRN BLK WHT BLU BLK BLK L3 OPTION 928 Digital Keypad OPTIONAL C NO Key Switch or Access Control Optional Typical System Wiring Pair of Doors Model 1511T REMOVE J6 ONLY IF A FIRE PANEL OR...

Page 7: ...COM DOOR POSITION SWITCH DPS BOND ALERT BAS PWR FP LOCK GRN RLY RED RLY RM TRIG RESET REX DPS BAS 12 VDC OR 24 VDC TO CLOSED FIRE SMOKE DETECTOR CONTACT SLAVE TANDEM LOCK POWER TERMINALS LOCK SECURE O...

Page 8: ...cycle expires MESSAGE TYPE The message type is selectable to MSG1 or MSG2 MSG1 Female Voice Exit in 12 seconds facility staff has been notified Exit in 5 seconds exit now MSG2 Male Voice Exit in 12 s...

Page 9: ...ter alignment has been verified close the door and apply power to the lock The digital display will show a two bars indicating that the lock is in the Manual Power Up mode Push on the door to verify t...

Page 10: ...dem Slave Lock Input DPS Door Position Status Optional BAS Magnetic Bond Status Optional ATS Anti Tamper Optional Alarm Output Lock Status Relay Output Door Secure Door Unlocked Specifications Interio...

Page 11: ...gger Power PT 2 PT 3 PTH 4 Hinge Switch Kit PUSHUNTILALARM SOUNDS DOORCANBE OPENEDIN15SECONDS PUSHUNTILALARM SOUNDS DOORCANBE OPENEDIN15SECONDS PUSHUNTILALARM SOUNDS DOORCANBE OPENEDIN15SECONDS PUSHUN...

Reviews: