SV600 Series User Manual 7 Parameter Description
165
Group AC: Correction of AI and AO
Function
code
Name
Setting range
Default
Property
AC-00
AI1 Measured Voltage 1
0.500 V ~ 4.000 V
Factory
calibrated
☆
AC-01
AI1 Display Voltage 1
0.500 V ~ 4.000 V
Factory
calibrated
☆
AC-02
AI1 Measured Voltage 2
6.000 V ~ 9.999 V
Factory
calibrated
☆
AC-03
AI1 Display Voltage 2
6.000 V ~ 9.999 V
Factory
calibrated
☆
AC-04
AI2 Measured Voltage 1
0.500 V ~ 4.000 V
Factory
calibrated
☆
AC-05
AI2 Display Voltage 1
0.500 V ~ 4.000 V
Factory
calibrated
☆
AC-06
AI2 Measured Voltage 2
6.000 V ~ 9.999 V
Factory
calibrated
☆
AC-07
AI2 Display Voltage2
6.000 V ~ 9.999 V
Factory
calibrated
☆
These parameters are used to correct the AI to eliminate the impact of AI zero offset and gain.
They have been corrected upon delivery.
Measured voltage indicates the actual output voltage value measured by instruments such as the
multimeter. Displayed voltage indicates the voltage display value sampled by the inverter.
During correction, provide two voltage values to each AI terminal, and save the measured values
and displayed values to the function codes AC-00 to AC-07. Then the inverter will automatically
perform AI zero offset and gain correction.
Function
code
Name
Setting range
Default
Property
AC-12
AO1 Target Voltage1
0.500 V ~ 4.000 V
Factory
calibrated
☆
AC-13
AO1 Measured Voltage 1
0.500 V ~ 4.000 V
Factory
calibrated
☆
AC-14
AO1 Target Voltage2
6.000 V ~ 9.999 V
Factory
calibrated
☆
AC-15
AO1 Measured Voltage 2
6.000 V ~ 9.999 V
Factory
calibrated
☆
AC-16
AO2 Target Voltage1
0.500 V ~ 4.000 V
Factory
calibrated
☆
AC-17
AO2 Measured Voltage 1
0.500 V ~ 4.000 V
Factory
calibrated
☆
AC-18
AO2 Target Voltage2
6.000 V ~ 9.999 V
Factory
calibrated
☆
AC-19
AO2 Measured Voltage2
6.000 V ~ 9.999 V
Factory
calibrated
☆
AC-20
AI2 Measured Current1
0.000 mA ~ 20.000 mA
Factory
calibrated
☆
AC-21
AI2 Sampling Current1
0.000 mA ~ 20.000 mA
Factory
☆