Shut down on
minimum freeze time
Grounded ice thickness sensor
Check sensor for dirt and
position. Clean and check gap.
Test Mode Sequence: - Air or Water Cooled
Time (seconds)
On
Off
0
WIV - 30 seconds
WP, HGV, Comp, Fan, PV
30
WP - 10 seconds
WIV, HGV, Comp, Fan, PV
40
WP, PV, HGV - 10 seconds
WIV, Comp, Fan
50
HGV, Comp - 5 seconds
WIV, WP, Fan, PV
55
Comp - 15 seconds
WIV, HGV, WP, Fan, PV
70
None - 5 seconds
All
75
HGV - 10 seconds
WIV, WP, Comp, Fan, PV
85
Fan - 10 seconds
WIV, HGV, WP, Comp, PV
95
None
All – Test Complete
September 2006 Page 49
Problem
Likely Cause
Probable Solution
Diagnostics - Water Cooled