4.3.2 CONTROL CYCLE (
CFG
>>
CtRL
)
This is the Control Cycle:
Control mode
This cycle allows you to configure the parameters that refer to the control mode and the device tuning process. See
chapter for more information about PID control and tuning processes.
Atun
Auto-tune
Allows you to define the tuning mode to be used:
off
– Disabled
Fast
– Fast auto-tuning
FULL
– Precise auto-tuning
seLf
– P auto-adaptive tuning
rsLf
– Forces a new p auto-adaptive auto-tuning
TGHt
– Forces a new p auto-tuning when
RUN
=
YES
or when the controller is on
pb
Proportional
Band
Proportional Band. Value of the
P
term of the PID control mode, in percent of the input type maximum
range. Adjustable between 0 and 500.0 %.
When set to 0.0 (zero), determines the ON/OFF control mode.
ir
integral rate
Integral Rate. Value of the
I
term of the PID control mode, in repetitions per minute (Reset). Adjustable
between 0 and 99.99. This parameter is displayed if the
Proportional Band
is
0.