scigiene N323R Operating Manual Download Page 1

TEMPERATURE CONTROLLER  

N323R

  

OPERATING MANUAL V1.7x 

 

 

The N323R is a Refrigeration controller designed to control the temperature of 
refrigeration cases and coldrooms, embedding several specialized functions for best 

system performance. The N323R can read two temperature probes (controller and 
defrost probes) and has three relay outputs for controlling the compressor, the defrost 

and the fan. 
The controller can be ordered with optional features such as to comply with the 
application’s requirements. The label on the instrument housing shows the complete 

instrument configuration. 

SPECIFICATIONS 

PROBE INPUT: ....................................................................................2 Thermistor NTC 
........................................................................................................ Type 10 k

Ω

 @ 25 °C 

.................................................................................Range: –50 to 120 °C (-58 to 248°F)  

............................................................................................................... Accuracy: 0,6 °C 

Two  3-meter probe cable are bundled with the instrument. The cable can be 

extended up to 200 m. Sensor interchangeability: 0,75 °C. This error can be 

compensated by the offset parameter in the controller. 

Measurement Resolution: ...................................................0,1 °C from –19.9º to 199.9º 

..................................................................................................................1 °C elsewhere 

OUTPUT1: ...................... Relay SPDT; 1 HP 250 Vac / 1/3 HP 125 Vac (16 A Resistive) 

 ...............................................Optionally: Pulse, 5 Vdc, 25 mA max. 

OUTPUT2:........Relay SPST-NA, 3 A / 250 Vac (General use) ;  5A / 250Vac (Resistive) 

 

OUTPUT3:.................. SPST-NA, 3 A / 250 Vac (General use) ;  5A / 250Vac (Resistive) 
POWER SUPPLY: 

............................... 100 to 240 Vca/dc  

±

10 % 

 Optionally:.................................... 12 to 30 Vdc 

 Mains 

frequency: ..............................50~60 Hz 

 Power 

consumption: ................................ 5 VA 

Dimensions

Width x Height x Depth:...................................75 x 33 x75 mm 

 Weight: ........................................................................... 100 g 

 Panel 

cut-out:.........................................................70 x 29 mm 

ENVIRONMENT: .................................. Operating temperature: 0 to 40 ºC (32 to 122 ºF) 
............................................................... Storage temperature: -20 to 60 ºC (-4 to 140 ºF) 
.................................................................. Relative humidity: 20 to 85 % non-condensing 

CASE:........................ Polycarbonate UL94 V-2; Protection: Front panel: IP65, Box: IP42 
...........................................................................................Suitable wiring: Up to 4,0 mm² 
DIGITAL COMMUNICATION: ....................... RS-485, RTU MODBUS protocol (optional) 

Serial interface not isolated from input circuitry. 

Serial interface isolated from input circuitry, except in 24 V powered model. 

INSTALLATION  

It is important to follow the recommendations below: 

  Signal wires should be installed in grounded conduits and away from power or 

contactor wires.  

 

The instrument should have its own power supply wires that should not be shared 

with electrical motors, coils, contactors, etc. 

  Installing RC filters (47 R and 100 nF, series combination) is strongly 

recommended at contactor coils or any other inductor. 

 

Use protection devices like circuit breakers and fuses. 

ELECTRICAL WIRING 

Figure 1 below shows the controller connections to sensor, mains and outputs. 

 

Figure 1 – N323R terminals 

OPERATION 

The controller requires the internal parameters to be configured according to the 
intended use for the instrument. The parameters are organized in 4 groups or levels: 

Level Function 

0 Temperature 

measurement 

1 Setpoint 

Adjustment 

2 Configuration 

3 Calibration 

Upon power-up, the N323R display shows for 1 second its firmware version. This 

information is useful when consulting the factory. 
Then, the temperature measured by the sensor is shown on the display. This is the 

parameter level 0 (temperature measurement level). 
To access level 1, press 

 for 1 second until the “

SP

” message shows up. Pressing 

 again to go back to level 0

To access level 2 of paramenters, press 

 for 2 seconds until the “

uNT

” message is 

shown. Release the 

 key to remain in this level. Each new pressing on the 

 key 

will advance to the next parameter in that level. At the end of the level, the controller 
returns to the first level (0). Use the 

 and 

 keys to alter a parameter value. 

Notes: 1 

parameter 

configuration is saved when the 

 

key is pressed to 

advance to the next parameter in the cycle. The configuration is stored 
in a non-volatile memory, retaining its value when the controller is de-

energized. 

2  If no keyboard activity is detected for over 20 seconds, the controller 

saves the current parameter value and returns to the measurement 

level. 

3. While in the temperature measurement level, a momentary pressing on 

the 

 key will show the Probe 2 temperature (evaporator temperature) 

Level 1 – Setpoint Adjustment 

In this level only the Setpoint (

SP

) parameters are available, alternating the names with 

their respective values. Adjust the desired temperature for each setpoint clicking on the 

 and 

 

keys. 

SP 

Set Point 

Case of coldroom temperate adjustment. 

SP

 value is limited to the 

values programmed in 

SPL

 and 

SPk 

in the programming level 

(Parameter configuration, level 2). 

Level 2 – Configuration – Parameters configuration Level 
Contains the configuration parameters to be defined by the user, according to the 
system’s requirements. Use 

 and 

 keys to set the value. The display alternates 

the parameter name and respective value. 

Unt 

Unit

 

Temperature  Unit. Selects display indication for degrees Celsius or 

Fahrenheit 

0

 Temperature 

Celsius. 

(factory 

default) 

1

  Temperature in degrees Fahrenheit. 

Of1 

Offset  

Probe 1 

Probe 1 Offset - Offset value to be added to the sensor 1 measured 
temperature such as to perform fine adjustments to the value showed on 

the display (after sensor replacement, for instance, if required). 
Range: ± 0.1 to 10.0 degrees. 

Of2 

Offset  

sensor 2

 

Probe 2 Offset - Offset value to be added to the sensor 2 measured 
temperature to perform fine adjustments to the value showed on the 

display  (after sensor replacement, for instance, if required). 

Range: ± 0.1 to 10.0 degrees. 

Spl 

SP Low Limit

 

SP Low Limit - Lower range for 

SP

.  

SPL 

must be programmed with a 

lower value than 

spK

spK 

SP High Limit

 

SP High Limit - Upper range for 

SP

.  

SPx 

must be greater than 

spl

Kys 

Histeresis

 

OUTPUT 1 Hysteresis: defines the differential range between the 

temperature value at which the OUTPUT is turned on and the value at 
which it is turned off. In degrees. 

(nt 

Control 

Defines the output position for the refrigeration relay. 

0

 

Refrigeration at OUTPUT1 / Defrost at OUTPUT2. (factory default) 

1

 

Refrigeration at OUTPUT2 / Defrost at OUTPUT1. 

Dly 

Delay

 

Delay time to start control. Upon power-on, control OUTPUT 1 is kept off 
until the time programmed in 

dly

 is elapsed.  Its usage is intended to 

prevent multiple compressors to start simultaneously after the turn-on of 

a system with several controllers.  Value in seconds, 0 to 250 s. 

0nt 

on time

 

On time - Defines the minimum on time for refrigeration output. Once 
turned on, OUTPUT 1 remains so for at least the time programmed in 

ont

. This parameter is intended for refrigeration systems where 

increased compressor life is desired. Value in seconds, 0 to 999 s. 

0ft 

Off time

 

Off time - Defines the minimum off time for control OUTPUT 1. Once 
OUTPUT 1 is turned off, it remains so for at least the time programmed 
in 

oft

. This parameter is intended for refrigeration systems where 

longer compressor life is desired.  Value in seconds, 0 to 999 s. 

df1 

Defrost 
Interval 

Interval time between defrost cycles. Adjustable from 0 to 999s. 

During this time, the defrost output remains off.  

df1= 0 

disables this function (no defrost cycles) 

Dft 

Defrost time 

Defrost duration. Interval time during which the defrost output remains 

on.    
Value in minutes,  1 to 999. 