By Soft
ware:
Allows logging to be started by means of a command from
NXperience
or
NOVUS Cloud.
•
By Soft
ware:
Allows logging to be started via an SMS co
mmand.
13.1.8.3
END MODE
•
Non-Stop:
Allows logging to continue indefinitely.
•
Date/Ti
me:
Allows for setting the Date/Time when the log
s should be concluded.
•
By Keypad:
Allows for changing the log status to disable
d on a display screen, stopping logging.
•
By Digital Input:
Allows logging to be paused at the digital input. This parameter will be available if the digital input is enabled and configured in
the "Log Control" mode. The logs will thus be paused as soon as the digital input is activated. The log edge should be configured in the digital
input parameters.
•
Daily:
Allows logg
ing to be concluded every day and at the configured time. A "Daily" log end mode requires a "Daily" log start mode.
•
By Soft
ware:
Allows logging to be terminated by means
of a command from
NXperience
or
NOVUS Cloud.
•
By Software:
Allows logging to be concluded via an SMS command.
The permitted combinations for starting and ending logs are
as follows:
Start Mode
I
mmediate
Date/Time
Digital Input
Keyboard
Software
Daily
SMS
End Modes
Non-Stop or Date/Time or Keypad or Digital Input or Software or SMS
Non-Sto
p or Date/Time or Keypad or Digital Input or Software or SMS
Non-Stop or Digital Input
Keyboard
Software
Daily
SMS
Table 31
– Log End Modes
13.1.8.4
PARAMETERS TO LOG/PUBLISH
Fig. 23
– Data Logging Screen: Local
This screen allows for selecting which data will be recorded to the device’s data memory ("Data Memory" tab) and which data will be published to
NOVUS Cloud
("Cloud" tab). The information can be saved simultaneously. In order to publish to
NOVUS Cloud
, data logging in the memory is
required.
13.1.8.4.1 DATA MEMORY
o
Analog Channel 1:
Enables/disables logging of analog channel 1 information.
o
Analog Channel 2:
Enables/disables logging of analog channel 2 information.
o
Digital Channel:
Enables/disables logging of periodic information about the digital channel. If the digital channel is in "Event Logging" or "Log
Control" mode and if this operation is enabled, the device will record the status of the digital input in the Logging Interval. Digital input events will
be logged asynchronously, whether or not this option is enabled.
o
Digital Channel Accumulator:
Enables/disables logging of information about the "Accumulator" function of the digital channel.
o
External Voltage Source:
Enables/disables logging of external power supply voltage information.
o
Battery Voltage (V):
Enables/disables logging of battery voltage information.
o
Battery Level (%):
Enables/disables logging of battery level information.
o
Internal Temperature:
Enables/disables logging of information about the device’s internal temperature.
o
GPS Coordinates:
Enables/disables logging of information about the device’s GPS coordinates.
42/66