D-2 Configuration,
Fast Meter,
and
Fast Operate
Commands
Date Code 990430
SEL-351P Manual Técnico
M
ESSAGE
D
EFINITIONS
A5C0 Relay Definition Block
In response to the A5C0 request, the SEL-351P sends the following block:
Data Description
A5C0 Command
34 Length
04
Support two protocols, SEL, M
IRRORED
B
ITS
™, DNP, and LMD
03 Support
three
Fast Meter
messages
03
Support three status flag commands
A5C1
Fast Meter
configuration command
A5D1
Fast Meter
command
A5C2 Demand
Fast Meter
configuration command
A5D2 Demand
Fast Meter
command
A5C3 Peak
Demand
Fast Meter
configuration command
A5D3 Peak
Demand
Fast Meter
command
0004
Settings change bit
A5C100000000
Fast Meter
configuration message
0004
Settings change bit
A5C200000000 Demand
Fast Meter
configuration message
0004
Settings change bit
A5C300000000 Peak
Demand
Fast Meter
configuration message
0100 SEL
protocol,
Fast Operate
0101 LMD
protocol,
Fast Operate
0005
DNP V3.00 protocol,
No Fast Operate
0006 M
IRRORED
B
ITS
protocol,
No Fast Operate
00 Reserved
checksum
1-byte checksum of preceding bytes
A5C1
Fast Meter
Configuration Block
In response to the A5C1 request, the SEL-351P sends the following block:
Data Description
A5C1
Fast Meter
command
84 Length
01
One status flag byte
00
Scale factors in
Fast Meter
message
00
No scale factors
0A
# of analog input channels
02
# of samples per channel
3C
# of digital banks
01
One calculation block
0004
Analog channel offset
0054
Time stamp offset
005C Digital
offset
494100000000
Analog channel name (IA)
01
Analog channel type
Summary of Contents for SEL-351P
Page 6: ......
Page 92: ......
Page 96: ......
Page 154: ......
Page 156: ......
Page 222: ......
Page 258: ......
Page 262: ......
Page 324: ......
Page 368: ......
Page 406: ......
Page 482: ......
Page 534: ......
Page 539: ......
Page 549: ......
Page 551: ......
Page 587: ......
Page 597: ......
Page 601: ......
Page 603: ......
Page 609: ......
Page 621: ......
Page 635: ......
Page 649: ......
Page 665: ......
Page 671: ......