Date Code 990215
Serial Port Communications and Commands
10-23
SEL-351P Manual Técnico
=>MET <ENTER>
RECLOSER R1 Date: 02/01/97 Time: 15:00:52.615
FEEDER 2101
A B C N G
I MAG (A) 195.146 192.614 198.090 0.302 4.880
I ANG (DEG) -8.03 -128.02 111.89 52.98 81.22
A B C S
V MAG (KV) 11.691 11.686 11.669 11.695
V ANG (DEG) 0.00 -119.79 120.15 0.05
A B C 3P
MW 2.259 2.228 2.288 6.774
MVAR 0.319 0.322 0.332 0.973
PF 0.990 0.990 0.990 0.990
LAG LAG LAG LAG
I1 3I2 3I0 V1 V2 3V0
MAG 195.283 4.630 4.880 11.682 0.007 0.056
ANG (DEG) -8.06 -103.93 81.22 0.12 -80.25 -65.83
FREQ (Hz) 60.00
=>
MET D – Demand Metering
The MET D command displays the demand and peak demand values of the following quantities:
Currents I
A,B,C,N
Input currents (A primary)
I
G
Residual ground current (A primary; IG =3I0 = IA + IB + IC)
3I
2
Negative-sequence current (A primary)
Power MW
A,B,C
Single-phase megawatts(wye-connected voltage inputs only)
MW
3P
Three-phase megawatts
MVAR
A,B,C
Single-phase megavars (wye-connected voltage inputs only)
MVAR
3P
Three-phase megavars
Reset Time
Demand, Peak Last time the demands and peak demands were reset
To view demand metering values, enter the command:
=>
MET D <ENTER>
Summary of Contents for SEL-351P
Page 6: ......
Page 92: ......
Page 96: ......
Page 154: ......
Page 156: ......
Page 222: ......
Page 258: ......
Page 262: ......
Page 324: ......
Page 368: ......
Page 406: ......
Page 482: ......
Page 534: ......
Page 539: ......
Page 549: ......
Page 551: ......
Page 587: ......
Page 597: ......
Page 601: ......
Page 603: ......
Page 609: ......
Page 621: ......
Page 635: ......
Page 649: ......
Page 665: ......
Page 671: ......