8-6
Breaker/Recloser Monitor, Battery System Monitor,
Date Code 990430
Metering, and Load Profile Functions
SEL-351P Manual Técnico
First, use the SET FZ (global EZ settings) command in Access Level E (EZ) or Access Level 2 to
make setting Recloser Wear Monitor (AUTO, Y, N) = Y. Then, in Access Level 2, use the SET
G (global settings) command to make the following SEL-351P contact wear monitor settings:
COSP1
=
10000
COSP2
=
150
COSP3
=
12
KASP1
=
1.20
KASP2
=
8.00
KASP3
=
20.00
Figure SECTION 8: .2 shows the resultant breaker maintenance curve.
Breaker Maintenance Curve Details
In Figure SECTION 8: .2, note that set points KASP1, COSP1 and KASP3, COSP3 are set with
breaker maintenance information from the two extremes in Table SECTION 8: .4 and
Figure SECTION 8: .1.
In this example, set point KASP2, COSP2 provides an intermediate breaker maintenance point in
the breaker maintenance information in Table SECTION 8: .4 and Figure SECTION 8: .1. Set
point KASP2, COSP2 should be set to provide the best “curve-fit” with the plotted breaker
maintenance points in Figure SECTION 8: .1.
Each phase (A, B, and C) has its own breaker maintenance curve (like that in Figure SECTION
8: .2), because the separate circuit breaker interrupting contacts for Phases A, B, and C don’t
necessarily interrupt the same magnitude current (depending on fault type and loading).
Summary of Contents for SEL-351P
Page 6: ......
Page 92: ......
Page 96: ......
Page 154: ......
Page 156: ......
Page 222: ......
Page 258: ......
Page 262: ......
Page 324: ......
Page 368: ......
Page 406: ......
Page 482: ......
Page 534: ......
Page 539: ......
Page 549: ......
Page 551: ......
Page 587: ......
Page 597: ......
Page 601: ......
Page 603: ......
Page 609: ......
Page 621: ......
Page 635: ......
Page 649: ......
Page 665: ......
Page 671: ......