10.6
SEL-2032
Communications Processor
Instruction Manual
Date Code 20120126
Testing and Troubleshooting
Relay Firmware Upgrades
CAUTION:
Equipment
components are sensitive to
electrostatic discharge (ESD).
Undetectable permanent damage
can result if you do not use proper
ESD procedures. Ground yourself,
your work surface, and this
equipment before removing any
cover from this equipment. If your
facility is not equipped to work with
these components, contact SEL
about returning this device and
related SEL equipment for service.
!
Step 4. Locate the battery on the front left-hand side of the main board.
Step 5. Remove the battery from beneath the clip and install a new one;
the positive side (+) of the battery faces up.
Step 6. Replace the front panel and front-panel screws and tighten
securely.
Step 7. Replace any cables removed from the SEL-2032.
Step 8. Apply power to the SEL-2032, and set the date and time again.
A battery failure will be reported the first time you power-up
with a new battery because the date and time reported by the
battery-backed clock will not be valid.
The SEL-2032 monitors the clock registers on power-up. If the clock registers
are invalid, the battery is presumed to be discharged and a battery failure is
reported.
Relay Firmware Upgrades
When you upgrade the firmware for an SEL relay attached to the SEL-2032,
perform the following steps:
Step 1. Take the relay out of service.
The SEL-2032 will show the relay’s port status as Inactive and
will no longer collect data.
Step 2. Upgrade the relay firmware according to its upgrade
instructions.
Step 3. Apply power to the relay and reset its settings, as necessary.
Step 4. Perform any relay testing that your practices require.
Step 5. Reconnect the relay to the SEL-2032, if necessary.
Step 6. Connect a computer terminal to the SEL-2032 and go to Access
Level 2.
Step 7. Make a backup copy of your SEL-2032 settings before
continuing with the next steps.
The backup settings may be needed if the SEL-2032 has auto
configuration problems with the upgraded relay causing
settings to be lost.
Step 8. Execute a
SET P
command on the relay’s port and auto-
configure the port; save these settings.
Step 9. Confirm that the SEL-2032 is now communicating as before.
Place the relay back in service.
Summary of Contents for SEL-2032
Page 6: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 12: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 46: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 70: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 104: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 124: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 188: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 216: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 244: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 322: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 328: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 336: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 338: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 342: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 348: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 354: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...