9.13
Date Code 20081022
Instruction Manual
SEL-787 Relay
Analyzing Events
Event Reporting
Figure 9.5
Derivation of Phasor RMS Current Values From Event Report
Current Values
Digital Event Report
(EVE D Command)
The digital event report includes:
➤
Digital states of control and protection elements, including
overcurrent and voltage elements (if voltage inputs are
available), plus status of digital inputs and outputs and RTD
status
➤
Event Summary
➤
Relay Settings
Use the
EVE D
n
command to view the normal digital report with 4 samples/
cycle for report
n
(if not listed,
n
is assumed to be 1).
EVE D R
gives the
RAW report with 16 samples/cycle.
Refer to the example event report in
to view the digital event report
columns.
IA (RMS)
t
IA
Event Report Column
Magnitude =
X = 940.7
Y = —750.3
Angle
= Arctan
= Arctan
Y
X
—750.3
940.7
= –38.6˚
Real Axis
Axis
Imaginary
1/4 cyc.
(—750.3)
2
+ (940.7)
2
= 1204
Y = Previous
1/4 Cycle
•
•
•
752.0
—941.0
—750.3
940.7
•
•
•
X = Present Sample
NOTE:
The arctan function of many
calculators and computing programs
does not return the correct angle for
the second and third quadrants (when
X is negative). When in doubt, graph
the X and Y quantities to confirm that
the angle that your calculator reports
is correct.
Summary of Contents for SEL-787
Page 1: ...20081022 SEL 787 Transformer Protection Relay Instruction Manual PM787 01 NB ...
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 78: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 280: ...This page intentionally left blank ...
Page 334: ...This page intentionally left blank ...
Page 376: ...This page intentionally left blank ...
Page 388: ...This page intentionally left blank ...
Page 474: ...This page intentionally left blank ...
Page 508: ...This page intentionally left blank ...