4.13
Date Code 20080918
Instruction Manual
SEL-749M Relay
Protection and Logic Functions
Basic Motor Protection
Figure 4.4
Ground Fault Protection Using Core-Balance CT
When a core balance CT is not available, use the 50G residual overcurrent
elements. Set the residual overcurrent trip level (50G1P) between one-half and
one-fifth of the full load phase current and set the residual overcurrent trip
delay (50G1D) equal to 0.2 seconds. Set the warn level more sensitively, but
with a longer time delay. The long time delay allows the sensitive warn
element to ride through the false residual current that can be caused by phase
CT saturation during motor starting.
Load Jam Elements
Load jam protection is available only when the relay detects that the motor is
in the RUNNING state. During a load jam condition, the motor stalls and the
phase current rises to near the locked rotor value. When load jam tripping is
enabled and the phase current exceeds the jam trip level setting (LJTPU) for
longer than the time delay setting (LJTDLY), the relay trips (see
).
Set the jam trip level greater than the expected normal load current but less
than the rated locked rotor current. This setting is entered in per unit of the full
load amps (FLA) setting.
Table 4.9
Residual Overcurrent Settings
Setting Prompt
Setting Range
Setting Name := Factory Default
RES OC TRIP LVL
Off, 0.10–1.00 xFLA
50G1P := OFF
RES OC TRIP DLAY
0.00–5.00 sec
50G1D := 0.50
RES OC WARN LVL
Off, 0.10–1.00 xFLA
50G2P := OFF
RES OC WARN DLAY
0.0–120.0 sec
50G2D := 10.0
10 A
C-Ground Fault
10 A
A
B
C
1 A
10:1
Window CT
Z0
7
Z0
8
Motor
NOTE:
Phase CT ratios are typically
higher than core balance (CB) CT
ratios. For this reason, the relay
sensitivity to motor ground faults is
less when the residual overcurrent
element is used instead of the CB
element. A separate ground fault
detection method should be used if a
CB CT is not available in applications
where resistance grounding reduces
the available ground fault current.
Table 4.10
Load Jam Settings
Setting Prompt
Setting Range
Setting Name := Factory Default
JAM TRIP LEVEL
Off, 1.00–6.00 xFLA
LJTPU := OFF
JAM TRIP DELAY
0.0–120.0 sec
LJTDLY := 0.5
JAM WARN LEVEL
Off, 1.00–6.00 xFLA
LJAPU := OFF
JAM WARN DELAY
0.0–120.0 sec
LJADLY := 5.0
Summary of Contents for SEL-749M
Page 6: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 14: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 20: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 32: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 52: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 118: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 188: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 216: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 224: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 274: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 286: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 306: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 310: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 314: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...