Testing and Troubleshooting
Periodic Tests (Routine Maintenance)
Periodic Tests (Routine Maintenance)
Because the SEL-749M is equipped with extensive self-tests, the most
effective maintenance task is to monitor the front-panel messages after a self-
test failure. In addition, each relay event report generated by a fault should be
reviewed. Such reviews frequently reveal problems with equipment external to
the relay, such as instrument transformers and control wiring.
The SEL-749M does not require specific routine tests, but your operation
standards may require some degree of periodic relay verification. If you need
or want to perform periodic relay verification, the following checks are
recommended.
Table 10.6
Power Quantity Accuracy—Delta Voltages
Applied Currents
and Voltages
Real Power
(kW)
Reactive Power
(kVAR)
Power Factor
(pf)
PHROT := ABC
Ia = 2.5
∠
–26
Ib = 2.5
∠
–146
Ic = 2.5
∠
+94
Expected:
P = 0.4677 •
CTR1 • PTR
Expected:
Q = 0.2286 •
CTR1 • PTR
Expected
pf = 0.90 lag
Vab = 120
∠
+30
Vbc = 120
∠
–90
Measured:
Measured:
Measured:
PHROT := ACB
Ia = 2.5
∠−
26
Ib = 2.5
∠
+94
Ic = 2.5
∠−
146
Expected:
P = 0.4677 •
CTR1 • PTR
Expected:
Q = 0.2286 •
CTR1 • PTR
Expected:
pf = 0.90 lag
Vab = 120
∠−
30
Vbc = 120
∠+
90
Measured:
Measured:
Measured:
Table 10.7
Periodic Relay Checks
Test
Description
Relay Status
Use the front-panel
STATUS
or serial port
STATUS
command to ver-
ify that the relay self-tests have not detected any WARN or FAIL con-
ditions.
Meter
Verify that the relay is correctly measuring current and voltage (if
included) by comparing the relay meter readings to separate external
meters.
Control Input
Using the front-panel
MAIN > Targets > Row 13
function,
check the control input status in the relay. As you apply rated voltage
to each input, the position in Row 13 corresponding to that input
should change from zero (0) to one (1).
Contact Output
For each output contact, set the input to Logic 1. This causes the output
contact to close. For example, setting OUT101 := 1 causes the output
OUT101
contact to close.
Repeat the process for all contact outputs. Make sure that each contact
closure does what you want it to do in the annunciation, control, or trip
circuit associated with that contact closure.
Summary of Contents for SEL-749M
Page 6: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 14: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 20: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 32: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 52: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 118: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 188: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 216: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 224: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 274: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 286: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 306: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 310: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 314: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...