701 Motor Protection Relay
Date Code 20010719
Commissioning
Relay Commissioning Procedure
7.4
current correctly, taking into account the relay PTR and CTR
settings and the fact that the quantities are displayed in primary
units. This step verifies the signal polarity and per-phase ac
connections to the relay.
Apply rated ac current (1 A or 5 A) to the relay IN input if used.
Use the front-panel or serial port
METER
function to verify that
the relay is measuring current magnitude and phase angle
correctly, taking into account the relay CTRN setting and the
fact that the quantities are displayed in primary units.
Figure 7.1
Three-Phase AC Connection Test Signals.
+120°
-120°
V
C
V
B
V
A
PHROT = ABC
+120°
-120°
PHROT = ACB
V
B
V
C
V
A
When setting PHROT = ABC, set angle Va
set angle Vb
set angle Vc
= angle Ia
= angle Ib
= angle Ic
= 0°
= -120°
= 120°
When setting PHROT = ACB, set angle Va
set angle Vb
set angle Vc
= angle Ia
= angle Ib
= angle Ic
= 0°
= 120°
= -120°
Summary of Contents for SEL-701
Page 12: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 20: ...This page intentionally left blank ...
Page 36: ...This page intentionally left blank ...
Page 64: ...This page intentionally left blank ...
Page 144: ...This page intentionally left blank ...
Page 198: ...This page intentionally left blank ...
Page 232: ...This page intentionally left blank ...
Page 246: ...This page intentionally left blank ...
Page 346: ...This page intentionally left blank ...
Page 390: ...This page intentionally left blank ...
Page 408: ...This page intentionally left blank ...
Page 410: ......
Page 412: ......
Page 414: ......
Page 416: ......
Page 418: ......
Page 420: ......
Page 422: ......
Page 424: ......
Page 426: ......
Page 428: ......
Page 430: ......
Page 432: ......
Page 434: ......
Page 436: ......
Page 438: ......
Page 440: ......
Page 442: ......
Page 452: ...This page intentionally left blank ...