Date Code 20011009
SEL-701-1 Monitor
Modbus
®
RTU Communications Protocol
03h Read Holding Registers Command
C.7
03h Read Holding Registers Command
Use function code 03h to read directly from the Modbus Register map shown in
. You may read a maximum of 125 registers at once with this
function code. Most masters use 4X references with this function code. If you are
accustomed to 4X references with this function code, for 5-digit addressing, add 40001
to the standard database address.
Table C.6
03h Read Holding Registers Command
Bytes
Field
The Master Request Must Have the Following Format
1 byte
Slave address
1 byte
Function code (03h)
2 bytes
Starting register address
2 bytes
Number of registers to read
2 bytes
CRC-16 for message
A Successful SEL-701-1 Monitor Response Will Have the Following Format
1 byte
Slave address
1 byte
Function code (03h)
1 byte
Byte count (should be twice number of registers read)
n bytes
Byte count bytes of data
2 bytes
CRC-16 for message