9.15
Date Code 20020903
SEL-587Z Instruction Manual
Event Reports and SER
Event Reports
(Continued from previous page)
DP7_1 = DP7_0 =
DP8_1 = DP8_0 =
SELogic Control Equations:
TR1 =87A1 + 87B1 + 87C1 + 50A1 + 50B1 + 50C1
TR2 =0
TR3 =0
ULTR1 =!87A2 * !87B2 * !87C2 * !50A2 * !50B2 * !50C2
ULTR2 =1
ULTR3 =1
51PTC =1
51ATC =1
51BTC =1
51CTC =1
51GTC =1
51QTC =1
52A =0
CL =0
ULCL =TRIP1
ER1 =87A1 + 87B1 + 87C1
ER2 =87A2 + 87B2 + 87C2
SV1 =0
SV2 =0
SV3 =0
SV4 =0
SV5 =0
SV6 =0
SV7 =0
SV8 =0
SV9 =0
SV10 =0
SV11 =0
SV12 =0
SV13 =0
SV14 =0
OUT1 =TRIP1
OUT2 =TRIP1
OUT3 =SV5T + SV6T
OUT4 =0
DP1 =0
DP2 =0
DP3 =0
DP4 =0
DP5 =0
DP6 =0
DP7 =0
DP8 =0
Figure 9.2
Example Event Report (1/4-cycle sample).
Obtaining RMS Phasors From 4-Samples/Cycle Event Reports
Sampling at 1/4-cycle generates data at 90-degree electrical intervals, thus
presenting the recorded values in the correct format for phasor calculations.
Similar calculations are possible with data generated using the
EVE L
command (1/8-cycle reports) by using every other row of analog values.
Use the column data in an event report to calculate phasor values. You can use
a calculator to convert rectangular data to phasor data.
Summary of Contents for SEL-587Z
Page 10: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 66: ...This page intentionally left blank ...
Page 106: ...This page intentionally left blank ...
Page 126: ...This page intentionally left blank ...
Page 162: ...This page intentionally left blank ...
Page 228: ...This page intentionally left blank ...