SEL-587Z Instruction Manual
ASCII Command Reference
Command Definitions
MET (Meter)
Access Levels 1, 2
The
MET
command displays instantaneous magnitudes and phase angles of
the following:
Current magnitudes are displayed in primary amperes. The SEL-587Z reports
the phase angles referenced to IA (IA phase angle = 0, positive phase angles
leading).
To view sequential instantaneous metering values, enter the command:
=>
MET
n
<Enter>
where
n
is an optional parameter to specify the number of times to repeat the
meter display.
n
may range from 1 to 32767. If
n
is not specified, the relay
displays the meter report once:
BUS 1 Date: 02/04/2002 Time: 15:29:43.170
STATION A
87A 87B 87C
V MAG (V) 0 0 0
IA IB IC IG 3I2
I MAG (A) 0 0 0 0 0
I ANG (DEG) 0.00 00.00 00.00 00.00 00.00
=>
MET D (Demand
Ammeter)
Access Levels 1, 2
The
MET D
command displays the demand and peak demand values of the
following quantities:
Element
Description
87A
A-phase high-impedance element measured voltage (magnitude only)
87B
B-phase high-impedance element measured voltage (magnitude only)
87C
C-phase high-impedance element measured voltage (magnitude only)
IA
A-phase current in primary amps
IB
B-phase current in primary amps
IC
C-phase current in primary amps
IG
Calculated residual current in primary amps
3I2
Calculated negative-sequence current in primary amps
Quantities
Description
Currents
I
A,B,C
input currents (A primary)
I
G
Residual ground current (A primary; IG =3I0 = IA + IB + IC)
3I
2
Negative-sequence current (A primary)
Reset Time
Demand, peak–last time the demands and peak demands were reset
Summary of Contents for SEL-587Z
Page 10: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 66: ...This page intentionally left blank ...
Page 106: ...This page intentionally left blank ...
Page 126: ...This page intentionally left blank ...
Page 162: ...This page intentionally left blank ...
Page 228: ...This page intentionally left blank ...