2.48
SEL-421 Relay
Instruction Manual
Date Code 20171021
Installation
Connection
The following list provides additional rules and practices you should follow for
successful communication using EIA-232 serial communications devices and
cables:
➤
Route communications cables well away from power and control
circuits. Switching spikes and surges in power and control circuits
can cause noise in the communications circuits if power and control
circuits are not adequately separated from communications cables.
➤
Keep the length of the communications cables as short as possible to
minimize communications circuit interference and also to minimize
the magnitude of hazardous ground potential differences that can
develop during abnormal power system conditions.
➤
Ensure that EIA-232 communications cable lengths never exceed
50 feet, and always use shielded cables for communications circuit
lengths greater than 10 feet.
➤
Modems provide communication over long distances and give
isolation from ground potential differences that are present between
device locations (examples are the SEL-28XX-series transceivers).
➤
Lower data speed communication is less susceptible to interference
and will transmit greater distances over the same medium than higher
data speeds. Use the lowest data speed that provides an adequate data
transfer rate.
Ethernet Network Connections
The optional Ethernet card for the SEL-421 comes with two ports, either A and B
or C and D. You can use either installed port. These ports can work together to
provide a primary and backup interface. Other operating modes (FIXED and
SWITCHED) are also available. The following list describes the Ethernet card
port options.
➤
10/100BASE-T. 10 Mbps or 100 Mbps communication using Cat 5
cable (category 5 twisted-pair) and an RJ45 connector
➤
100BASE-FX. 100 Mbps communication over multimode fiber-optic
cable using an LC connector
Ethernet Card Rear-Panel Layout
Rear-panel layouts for the three Ethernet card port configurations are shown in
–
Figure 2.48
Example Ethernet Panel With Fiber-Optic Ports
Optional fiber-optic ports
CAUTION
Use of controls or adjustments, or
performance of procedures other
than those specified herein, may
result in hazardous radiation expo-
sure.
WARNING
Do not look into the fiber ports/con-
nectors.
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...