5.41
Date Code 20171006
Instruction Manual
SEL-400 Series Relays
Control
Bay Control Example Application
Table 5.6
Application Example Bay Control Settings for Bus 1, Bus 2, and
Transfer Bus Bay With Ground Switch Application (Sheet 1 of 2)
Setting
Description
Entry
General One-Line Settings
MIMIC
One-line Screen Number (1–999)
4
BAYNAME
Bay Name (20 characters)
BAY CONTROL
Busbar Information
BUSNAM1
Busbar 1 Name (40 pixels, 6–10 characters)
Bus T
BUSNAM2
Busbar 2 Name (40 pixels, 6–10 characters)
Bus 2
BUSNAM3
Busbar 3 Name (40 pixels, 6–10 characters)
Bus 1
Breaker Information
B1HMINM
Breaker 1 HMI Name (max 3–17 characters)
Bkr 1
B1CTLNM
Breaker 1 HMI Cntl Scr. Name (max. 15 characters)
Bkr 1
521CLSM
Breaker 1 Close Status (SEL
OGIC
Equation)
52ACL1
521_ALM
Breaker 1 Alarm Status (SEL
OGIC
Equation)
52AAL1
Disconnect Information
D1HMIN
Disconnect 1 HMI Name (max 3–17 characters)
D1
D1CTLN
Disconnect 1 Name (25 pixels, max. 15 characters)
Dis 1
89AM1
Disconnect 1 N/O Contact (SEL
OGIC
Equation)
IN103
89BM1
Disconnect 1 N/C Contact (SEL
OGIC
Equation)
IN104
89ALP1
Disconnect 1 Alarm Pickup Delay (1–99999 cyc)
260
89CCN1
Disconnect 1 Close Control (SEL
OGIC
Equation)
89CC01
89OCN1
Disconnect 1 Open Control (SEL
OGIC
Equation)
89OC01
89CST1
Disconnect 1 Close Seal-in Time (1–99999 cyc)
280
89OST1
Disconnect 1 Open Seal-in Time (1–99999 cyc)
280
D2HMIN
Disconnect 2 HMI Name (max. 3–17 characters)
D2
D2CTLN
Disconnect 2 Name (25 pixels, 4–6 characters)
Dis 2
89AM2
Disconnect 2 N/O Contact (SEL
OGIC
Equation)
1
89BM2
Disconnect 2 N/C Contact (SEL
OGIC
Equation)
0
89ALP2
Disconnect 2 Alarm Pickup Delay (1–99999 cyc)
260
89CCN2
Disconnect 2 Close Control (SEL
OGIC
Equation)
89CC02
89OCN2
Disconnect 2 Open Control (SEL
OGIC
Equation)
89OC02
89CST2
Disconnect 2 Close Seal-in Time (1–99999 cyc)
280
89OST2
Disconnect 2 Open Seal-in Time (1–99999 cyc)
280
D3HMIN
Disconnect 3 HMI Name (max. 3–17 characters)
D3
D3CTLN
Disconnect 3 Name (25 pixels, 4–6 characters)
Dis 3
89AM3
Disconnect 3 N/O Contact (SEL
OGIC
Equation)
1
89BM3
Disconnect 3 N/C Contact (SEL
OGIC
Equation)
0
89ALP3
Disconnect 3 Alarm Pickup Delay (1–99999 cyc)
260
89CCN3
Disconnect 3 Close Control (SEL
OGIC
Equation)
89CC03
89OCN3
Disconnect 3 Open Control (SEL
OGIC
Equation)
89OC03
89CST3
Disconnect 3 Close Seal-in Time (1–99999 cyc)
280
89OST3
Disconnect 3 Open Seal-in Time (1–99999 cyc)
280
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...