Date Code 20171006
Instruction Manual
SEL-400 Series Relays
Basic Relay Operations
Operating the Relay Inputs and Outputs
c. Type
IN101 <Enter>
at the
?
prompt to specify input IN101 as
the control input that represents the close/open state of Circuit
Breaker 1.
Press
<Enter>
until the relay displays the 52AA2 SEL
OGIC
control equation action prompt.
d. Type
IN102 <Enter>
at the
?
prompt to specify input IN102 as
the control input that represents the close/open state of Circuit
Breaker 2.
Step 3. End the settings process. The relay next scrolls a readback of all the
Global settings, eventually displaying the
Save settings (Y,N) ?
prompt.
a. In the readback information, just before the
Save settings
(Y,N) ?
prompt, confirm the new control input information.
b. Answer
Y <Enter>
to save your new settings.
Setting a Control Input for Circuit Breaker Auxiliary Contacts (52A) in
QuickSet
The procedure in the following steps shows how to program the relay control
input IN101 to read the state of circuit breaker auxiliary contacts. This example
uses a single three-pole tripping breaker. Modify the procedure listed here for
your application.
This example assumes that you have successfully established communication
with the relay (see
Making an EIA-232 Serial Port Connection on page 3.4
). In
addition, you must be familiar with relay access levels and passwords (see
Changing the Default Passwords in the Terminal on page 3.10
to change the
default access level passwords). You should also be familiar with QuickSet (see
Step 1. Start QuickSet and establish a connection with the relay. See Step 1
and Step 2 of
Checking Relay Status in QuickSet on page 3.12
for
detailed steps.
Step 2. On the
File
menu, click
Read
.
The relay sends all configuration and settings data to QuickSet.
=>>
SET M <Enter>
Breaker Monitor
Breaker Configuration
Breaker 1 Monitoring (Y,N) EB1MON := N
? <Enter>
Breaker 2 Monitoring (Y,N) EB2MON := N
? <Enter>
Breaker 1 Inputs
N/O Contact Input -BK1 (SELogic Equation)
52AA1 := NA
?
IN101 <Enter>
Breaker 2 Inputs
N/O Contact Input -BK2 (SELogic Equation)
52AA2 := NA
?
IN102 <Enter>
Breaker Monitor
Breaker Configuration
EB1MON := N EB2MON := N
Breaker 1 Inputs
52AA1 := IN101
Breaker 2 Inputs
52AA2 := IN102
Save settings (Y,N) ?
Y <Enter>
Saving Settings, Please Wait...........
Settings Saved
=>>
Figure 3.63
Setting 52AA1 in the Terminal
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...