![Schweitzer Engineering Laboratories SEL-421-4 Instruction Manual Download Page 513](http://html.mh-extra.com/html/schweitzer-engineering-laboratories/sel-421-4/sel-421-4_instruction-manual_1216726513.webp)
6.177
Date Code 20171021
Instruction Manual
SEL-421 Relay
Protection Applications Examples
230 kV Tapped Transmission Line Application Example
PST02R
Protection Sequence Timer 2 reset
PST02R := PLT01
PST02IN
Protection Sequence Timer 2 enable
PST02IN := PSV02 AND IN103
230 kV bus is dead AND MOD is open
PST03PT
Protection Sequence Timer 3 preset
PST03PT := 3600.00
MOD latch reset if:
PST03R
Protection Sequence Timer 3 reset
PST03R := NOT PLT01
PST03IN
Protection Sequence Timer 3 enable
PST03IN := PSV01 AND IN101 AND
IN102
230 kV bus is hot AND BK1T AND
BK2T are open for 60 s
PST04PT
Protection Sequence Timer 4 preset
PST04PT := 330.00
Pulse close the MOD if:
PST04R
Protection Sequence Timer 4 reset
PST04R := NOT PSV01 OR NOT
IN101 OR NOT IN102 OR NOT IN103
OR PLT01 OR PST04Q
230 kV bus is not hot OR BK1T OR
BK2T is closed OR MOD is closed OR
PST04 output equals logical 1
PST04IN
Protection Sequence Timer 4 enable
PST04IN := PSV01 AND IN101 AND
IN102 AND IN103 AND NOT PLT01
230 kV bus is hot AND BK1T AND
BK2T are open AND MOD is open
AND MOD latch reset
OUT106*
Output 106 AND NOT PCN02Q
PST04ET > 300.00 AND NOT PCN02Q MOD close command
PCN01PV
Protection Counter 1 preset
PCN01PV := 2
MOD block trip if:
PCN01R
Protection Counter 1 reset
PCN01R := IN103
PCN01IN
Protection Counter 1 enable
PCN01IN := OUT103
Two trips without MOD open
PCN02PV
Protection Counter 2 preset
PCN02PV := 2
MOD block close if:
PCN02R
Protection Counter 2 reset
PCN02R := NOT IN103
PCN02IN
Protection Counter 2 enable
PCN02IN := OUT106
Two closes without MOD closed
PCT01PU
Protection Conditioning Timer 1
Pickup
240.00
PCT01DO
Protection Conditioning Timer 1
Dropout
0.00
PCT01IN
Protection Conditioning Timer 1
Enable
NOT IN103 AND 25A1BK1 OR PLT01
AND IN103 AND 59VS1
MOD is closed AND synchronized OR
MOD latch set AND MOD is open
AND BK1T bus is hot for 4 s
PCT02PU
Protection Conditioning Timer 2
Pickup
240.00
PCT02DO
Protection Conditioning Timer 2
Dropout
0.00
PCT02IN
Protection Conditioning Timer 2
Enable
NOT IN103 AND 25A1BK2 AND NOT
IN101 OR PLT01 AND IN103 AND
59VS2 AND NOT IN101
MOD is closed AND synchronized
AND BK1T is closed OR MOD latch
set AND MOD is open AND BK2T bus
is hot AND BK11T is closed for 4 s
a
This control output assignment is not a protection freeform SEL
OGIC
control equation, but appears in this table for continuity of the overall
logic.
Table 6.48
Protection Freeform SEL
OGIC
Control Equations (Sheet 2 of 2)
Setting
Description
Entry
Comments
=>>
SHO L <Enter>
Protection 1
Free-Form Protection SELogic
1: ### PROTECTION FREE-FORM AUTOMATION EXAMPLE
2: ###
3: ### SET CONTROL VARIABLE 1
4: ### ASSERTS WHEN PRIMARY POSITIVE SEQUENCE VOLTAGE IS
5: ### GREATER THAN 90% OF NOMINAL
Figure 6.53
Protection Free-Form SEL
OGIC
Control Equations
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...