1.18
SEL-421 Relay
Instruction Manual
Date Code 20171021
Introduction and Specifications
Specifications
Zones 4 and 5
5 A Model:
OFF, 0.05 to 150
secondary, 0.01
steps
1 A Model:
OFF, 0.25 to 750
secondary, 0.01
steps
Sensitivity
5 A Model:
0.5 A secondary
1 A Model:
0.1 A secondary
Accuracy (Steady State):
±3% of setting at line angle for SIR < 30
±5% of setting at line angle for
30
SIR
60
Transient Overreach:
<5% of setting
plus
steady-state accuracy
Mho Ground-Distance Elements
Zones 1–5 Impedance Reach
Mho Element Reach
5 A Model:
OFF, 0.05 to 64
secondary, 0.01
steps
1 A Model:
OFF, 0.25 to 320
secondary, 0.01
steps
Sensitivity
5 A Model:
0.5 A secondary
1 A Model:
0.1 A secondary
(Minimum sensitivity is controlled by the
pickup of the supervising phase and residual
overcurrent elements for each zone.)
Accuracy (Steady State):
±3% of setting at line angle for SIR < 30
±5% of setting at line angle for
30
SIR
60
Zone 1 Transient
Overreach:
<5% of setting
plus
steady-state accuracy
SEL-421-5 Maximum
Operating Time:
0.8 cycle at 70% of reach and SIR = 1
SEL-421-4 Maximum
Operating Time:
1.5 cycle at 70% of reach and SIR = 1
Quadrilateral Ground-Distance Elements
Zones 1–5 Impedance Reach
Quadrilateral Reactance Reach
5 A Model:
OFF, 0.05 to 64
secondary, 0.01
steps
1 A Model:
OFF, 0.25 to 320
secondary, 0.01
steps
Quadrilateral Resistance Reach
Zones 1, 2, and 3
5 A Model:
OFF, 0.05 to 50
secondary, 0.01
steps
1 A Model:
OFF, 0.25 to 250
secondary, 0.01
steps
Zones 4 and 5
5 A Model:
OFF, 0.05 to 150
secondary, 0.01
steps
1 A Model:
OFF, 0.25 to 750
secondary, 0.01
steps
Sensitivity
5 A Model:
0.5 A secondary
1 A Model:
0.1 A secondary
(Minimum sensitivity is controlled by the
pickup of the supervising phase and residual
overcurrent elements for each zone.)
Accuracy (Steady State):
±3% of setting at line angle for SIR < 30
±5% of setting at line angle for
30
SIR
60
Transient Overreach:
<5% of setting plus steady-state accuracy
Instantaneous/Definite-Time Overcurrent Elements
Phase, Residual Ground, and Negative-Sequence
Pickup Range
5 A Model:
OFF, 0.25–100.00 A secondary,
0.01 A steps
1 A Model:
OFF, 0.05–20.00 A secondary,
0.01 A steps
Accuracy (Steady State)
5 A Nominal:
±0.05 A plus ± 3% of setting
1 A Nominal:
±0.01 A plus ± 3% of setting
Transient Overreach:
<5% of pickup
Time-Delay:
0.00–16000.00 cycles, 0.125 cycle steps
Timer Accuracy:
±0.125 cycle plus ± 0.1% of setting
Maximum
Operating Time:
1.5 cycles
Time-Overcurrent Elements
Pickup Range
5 A Model:
0.25–16.00 A secondary, 0.01 A steps
1 A Model:
0.05–3.20 A secondary, 0.01 A steps
Accuracy (Steady State)
5 A Model:
±0.05 A plus ± 3% of setting
1 A Model:
±0.01 A plus ± 3% of setting
Time Dial Range
US:
0.50–15.00, 0.01 steps
IEC:
0.05–1.00, 0.01 steps
Curve Timing Accuracy:
±1.50 cycles plus ± 4% of curve time (for
current between 2 and 30 multiples of
pickup)
Reset:
1 power cycle or Electromechanical Reset
Emulation time
Ground Directional Elements
Neg.-Seq. Directional Impedance Threshold (Z2F, Z2R)
5 A Model:
–64 to 64
1 A Model:
–320 to 320
Zero-Seq. Directional Impedance Threshold (Z0F, Z0R)
5 A Model:
–64 to 64
1 A Model:
–320 to 320
Supervisory Overcurrent Pickup 50FP, 50RP
5 A Model:
0.25 to 5.00 A 3I0 secondary
0.25 to 5.00 A 3I2 secondary
1 A Model:
0.05 to 1.00 A 3I0 secondary
0.05 to 1.00 A 3I2 secondary
Undervoltage and Overvoltage Elements
Pickup Ranges
Phase Elements:
2–300 V secondary, 0.01 V steps
Phase-to-Phase
Elements:
4–520.0 V secondary, 0.01 V steps
Accuracy (Steady State):
±0.5 V plus ± 5% of setting
Transient Overreach:
<5% of pickup
Underfrequency and Overfrequency Elements
Pickup Range:
40.01–69.99 Hz, 0.01 Hz steps
Accuracy, Steady State
Plus Transient:
±0.005 Hz for frequencies between 40.00
and 70.00 Hz
Maximum Pickup/
Dropout Time:
3.0 cycles
Time-Delay Range:
0.04–400.0 s, 0.01 s increments
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...