Open-Phase Detection Logic
Open-Phase Detection Logic
Some line-relaying applications (e.g., circuit breaker failure protection) benefit
from fast open-phase detection. The resetting time of the instantaneous overcur-
rent elements using filtered quantities can be extended after the corresponding
phase(s) is open if subsidence current is present. The SEL-421 open-phase detec-
tor senses an open phase in less than one cycle. This information is used for pur-
poses such as quickly disabling instantaneous overcurrent elements in the circuit
breaker failure schemes and open-pole detection.
The open-phase detection logic uses both the half-cycle and one-cycle cosine
digital filter data shown in
Figure 9.2 on page 9.5 in the SEL-400 Series Relays
Instruction Manual
to achieve the high-speed response to an open-phase condi-
tion.
lists the output Relay Word bits.
Table 5.20
Fault Type
Label
Fault Type
AG
A-Phase-to-ground
BG
B-Phase-to-ground
CG
C-Phase-to-ground
AB
A-Phase-to-B-Phase
BC
B-Phase-to-C-Phase
CA
C-Phase-to-A-Phase
ABG
A-Phase-to-B-Phase-to-ground
BCG
B-Phase-to-C-Phase-to-ground
CAG
C-Phase-to-A-Phase-to-ground
ABC
Three-phase
Table 5.21
Fault Location Settings
Setting
Prompt
Range
Default
(5 A)
Z1MAG Positive-Sequence Line Impedance Magnitude (
)
(0.25–1275)/I
NOM
7.80
Z1ANG
Positive-Sequence Line Impedance Angle (°)
5.00–90
84.00
Z0MAG Zero-Sequence Line Impedance Magnitude (
)
(0.25–1275)/I
NOM
24.80
Z0ANG
Zero-Sequence Line Impedance Angle (°)
5.00–90
81.50
EFLOC
Fault Location
Y, N
Y
LL
Line Length
0.10–999
100.00
Table 5.22
Fault Location Relay Word Bit
Name
Description
RSTFLOC
Fault locator analog quantity reset in progress.
a
a
Use Global setting RSTFLOC shown in
to reset the stored fault location
analog quantity FLOC. Relay Word bit RSTFLOC will assert momentarily while the clearing action
proceeds.
When reset, the value contained in FLOC is set to a very large number (greater than 1037).
Resetting this value has no effect on the event reports stored in the SEL-421, nor does it have an
effect on DNP3 event access.
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...