14.56
SEL-400 Series Relays
Instruction Manual
Date Code 20171006
ASCII Command Reference
Command Description
TEST DB OFF
Use the
TEST DB OFF
command to end the testing session and remove the
override values. The relay returns the database registers to the pretest values.
TEST DB2
The
TEST DB2
command is used to test DNP3 and IEC 61850 MMS communi-
cation protocols.
TEST DB2
Other than Fast Message Protocol, all the communication protocols supported by
the relay (DNP3, IEC 61850, GOOSE) retrieve data from a storage area called
the CADI2 database. These data include both digital quantities and analog quan-
tities. All Relay Word bits along with additional binary input points in DNP3
map are available in CADI2 database as digital quantities.
Use the
TEST DB2
command to override any value in the CADI2 database. Val-
ues you enter in the CADI2 database are override values read by the master sta-
tions.
The override value
value1
can be logical 0 or logical 1 for digital and status ele-
ments. The analog
value2
can be an integer or a floating-point number.
The Relay Word bit TESTDB2 will be asserted while there are points in this test
mode.
Table 14.130
TEST DB OFF Command
Command
Description
Access Level
TEST DB OFF
Clear all override testing values from all virtual devices.
B, P, A, O, 2
TEST DB OFF 1
Clear all override testing values from Virtual Device 1
(the relay).
B, P, A, O, 2
TEST DB OFF 1
region
Clear all override testing values from the region
region
in
Virtual Device 1 (the relay).
B, P, A, O, 2
Table 14.131
TEST DB2 Command
Command
Description
Access Level
TEST DB2
Display present analog and digital override names and
values.
1, B, P, A, O, 2
TEST DB2 D
name1
a
value1
a
Digital
name1
can be any Relay Word bits or additional binary input points in DNP3 map.
Write the specified override value
value1
into the digital
quantity
name1
.
B, P, A, O, 2
TEST DB2 A
name2
b
value2
b
The analog
name2
is any analog available in the DNP3 reference map and any analog listed as a
data source for IEC 61850 logical devices.
Write the specified override value
value2
into the analog
quantity
name2
.
B, P, A, O, 2
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...