8.16
SEL-400 Series Relays
Instruction Manual
Date Code 20171006
Monitoring
Circuit Breaker Monitor
Figure 8.8
Pole Discrepancy Measurement
Example 8.8
Pole Discrepancy Alarm for Circuit Breaker 1—No Other Circuit
Breaker Monitor Functions
Use Circuit Breaker 1, a single-pole tripping circuit breaker, for this exam-
ple. This example uses control inputs IN301, IN302, and IN303 for the A-,
B-, and C-Phases, respectively; you can use any control inputs that are
appropriate for your installation.
The control voltage for this example is 125 Vdc. Control Inputs IN301–
IN303 are located on I/O Board #2. Connect the circuit breaker normally
open auxiliary circuit breaker (52A) contacts through station battery power
to IN301, IN302, and IN303.
Set the relay internal Relay Word bits to respond to these inputs by using the
QuickSet
Breaker Monitor (SET M)
settings:
52AA1 :=
IN301
A-Phase Normally Open Control Input—BK1
(SEL
OGIC
Equation)
52AB1 :=
IN302
B-Phase Normally Open Control Input—BK1
(SEL
OGIC
Equation)
52AC1 :=
IN303
C-Phase Normally Open Control Input—BK1
(SEL
OGIC
Equation)
Connect external trip signals to IN301, IN302, and IN303, and external close
signals to IN304, IN305, and IN306 for the A-, B-, and C-Phases, respec-
tively. This example uses control inputs IN301–IN306; you can use any con-
trol inputs that are appropriate for your installation.
Set the pole discrepancy time delay (B1PDD) at 1400 ms. This time delay
assumes a dead time of 1000 ms plus a pole closing time of 100 ms (includ-
ing contact latency), plus 20 percent (for security), rounded to the next
higher hundreds of milliseconds value. This pole discrepancy time is longer
than the single-pole open interval time default of 900 ms; confirm that this is
the case for your application settings.
Enter the following settings:
B1PDD :=
1400
Pole Discrepancy Time Delay—BK1 (1–9999 ms)
EB1MON :=
Y
Breaker 1 Monitoring (Y, N)
BK1TYP :=
1
Breaker 1 Trip Type (Single Pole = 1, Three Pole = 3)
The pole discrepancy timing window is B1PDD := 1400 (ms). Assertion of
the Relay Word bit B1PDAL indicates that the status of the three Circuit
Breaker 1 poles disagrees for 1400 ms or longer.
All Poles Open
Pole B: 52AB1
Pole C: 52AC1
Pole A: 52AA1
Pole
Discrepancy
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...