7.2
SEL-400 Series Relays
Instruction Manual
Date Code 20171006
Metering
Instantaneous Metering
Instantaneous Metering
Use instantaneous metering to monitor power system parameters in real time.
The relay typically provides these fundamental frequency readings:
➤
Fundamental frequency phase voltages and currents
➤
Phase-to-phase voltages
➤
Sequence voltages and currents
➤
Fundamental real, reactive, and apparent power
➤
Displacement power factor
NOTE:
After startup, automatic
restart, or a warm start, including
settings change and group switch, in
the beginning period of 20 cycles, the
10-cycle average values are initialized
with the latest calculated 1-cycle
average values.
You can also typically monitor these real-time rms quantities (with harmonics
included):
➤
RMS phase voltages and currents
➤
Real and apparent rms power
➤
True power factor
Power
The instantaneous power measurements are derived from 10-cycle averages that
the relay reports by using the generator condition of the positive power flow con-
vention; for example, real and reactive power flowing out (export) is positive, and
real and reactive power flowing in (import) is negative (see
NOTE:
The SEL-487B does not
include power and power factor in its
metering reports.
For power factor, LAG and LEAD refer to whether the current lags or leads the
applied voltage. The reactive power Q is positive when the voltage angle is
greater than the current angle (
V >
I), which is the case for inductive loads
where the current lags the applied voltage. Conversely, Q is negative when the
voltage angle is less than the current angle
V <
I); this is when the current
leads
the voltage, as in the case of capacitive loads.
MET M
Display line maximum/minimum metering information
MET RM
Reset line maximum/minimum metering information
MET D
Display demand line metering information
MET RD
Reset demand line metering information
MET RP
Reset peak demand line metering information
MET E
Display energy line metering information
MET RE
Reset energy line metering information
MET BAT
Display dc battery monitor information
MET RBM
Reset battery monitor min/max measurements
MET PM
Display phasor measurement (synchrophasor) metering information
MET RTD
Display SEL-2600 temperature quantities
MET PMV
Display protection math variable values
MET AMV
Display automation math variable values
MET ANA
Display remote analogs received from M
IRRORED
B
ITS
Table 7.1
MET Command (Sheet 2 of 2)
Name
Description
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...