6.40
SEL-400 Series Relays
Instruction Manual
Date Code 20171006
Autoreclosing
Manual Closing
Manual Closing
Manual closing is available via the relay to issue a close to the circuit breaker(s)
via the same close logic outputs used in autoreclosing (Relay Word bits BK1CL
and BK2CL for as many as two circuit breakers). The manual close logic can be
user-configured in most any manner with SEL
OGIC
settings BK1MCL and
BK2MCL.
is a flowchart of the manual close logic. This logic is
enabled with Manual Closing enable setting EMANCL := Y.
only details the manual close logic for one circuit breaker (breaker
BK1). The manual close logic for a second circuit breaker (breaker BK2), if
enabled (Global setting NUMBK := 2), is similar. The only difference between
the breaker BK1 and breaker BK2 manual close logic in
is the substi-
tution of settings and logic outputs (BK2MCL for BK1MCL, ULCL2 for
ULCL1, etc.). A manual close is issued for breaker BK1 if all of the following are true:
➤
A new manual close signal for breaker BK1 is detected (rising edge
assertion of SEL
OGIC
setting BK1MCL)
➤
No unlatch close conditions are present (SEL
OGIC
setting ULCL1
deasserted)
➤
No close is presently in progress for breaker BK1 (Relay Word bit
output BK1CL is deasserted)
If a manual close is successfully issued for breaker BK1, then:
➤
Close logic output BK1CL asserts
➤
The close failure timer starts timing
Figure 6.16
Two Circuit Breakers Three-Pole Cycle State (79CY3) When E79 := Y1 (Continued)
D
12
3
6
9
Is 79BRCT Asserted?
Recalculate NBKn,
Leader, and Follower
Determine
Active Breakers
Determine Leader
Timing
3PARC
3PARC
To beginning
of 79CY3
*Send Breakers (not already
in the Lockout State, e.g., BKnL0)
to the Reset State (BKnRS)
Breaker #1
Ready State (BK1RS)
Breaker #2
Ready State (BK2RS)
No
Yes
NBK1
LEADBK1
LEADBK2
NBK2
Timed Out
Reclaim Timer
(3PRCD)
Breaker Open
Lockout
(BKnLO)
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...