E-8
Compressed ASCII Commands
Date Code 20010521
SEL-387E Instruction Manual
CSTATUS C
OMMAND
Display the SEL-387E Relay Compressed ASCII status report by sending:
CST <ENTER>
The relay sends:
<STX>
"FID","yyyy"<CR>
"FID=SEL-387E-XXXX-V-ZXXXXXX-DXXXXXXXX","yyyy"<CR>
"MONTH_","DAY_","YEAR_","HOUR_","MIN_","SEC_","MSEC_","yyyy"<CR>
xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,"yyyy"<CR>
"IAW1","IBW1","ICW1","IAW2","IBW2","ICW2","IAW3","IBW3","ICW3", "VAWX",
"VBWX","VCWX",
"+5V_PS","+5V_REG","-5V_REG","+12V_PS","-12V_PS","+15V_PS",
"-15V_PS","TEMP","RAM","ROM","A/D","CR_RAM","EEPROM","IO_BRD","yyyy"<CR>
"xxxx","xxxx","xxxx","xxxx","xxxx","xxxx","xxxx","xxxx","xxxx","xxxx","xxxx","xxxx",
"xxxx","xxxx","xxxx","xxxx","xxxx","xxxx","xxxx","xxxx","xxxx","xxxx","xxxx", "xxxx",
"xxxx", "xxxx", “yyyy"<CR>
<ETX>
where
xxxx are the data values corresponding to the first line labels.
yyyy is the 4-byte ASCII representation of the hex checksum for the line.
Note
: If the analog current input names (IAW1, etc.) have been changed via the Analog Input
Labels global settings, they will appear in the above report as set.
CTARGET C
OMMAND
Display the SEL-387E Relay Compressed ASCII target display by sending:
CTA N <ENTER>
Where N is one of the target numbers or element names accepted by the
TAR
command. If N is
omitted, 0 is used.
The relay responds:
<STX>
"LLLL","LLLL","LLLL","LLLL","LLLL","LLLL","LLLL","LLLL","yyyy"<CR>
x,x,x,x,x,x,x,x,"yyyy"<CR>
<ETX>
where
LLLL are the labels for the given target.
x is 0 or 1 corresponding to the first line labels.
yyyy is the 4-byte ASCII representation of the hex checksum for the line.