Date Code 20010521
Compressed ASCII Commands
E-5
SEL-387E Instruction Manual
xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,
xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx"yyyy"<CR>
xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,
xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx"yyyy"<CR>
xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,
xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx"yyyy"<CR>
<ETX>
where
The data are a summation of breaker information collected since the last summary
clear.
xxxx are the data values corresponding to the first line labels.
yyyy is the 4-byte ASCII representation of the hex checksum for the line.
CEVENT C
OMMAND
The CEV report contains every analog and digital element found in an EVE report, and displays
the information in Compressed ASCII format by sending:
CEV [DIF R] [n Sx Ly[-[w]] C] <ENTER>
The command parameters, all optional, can be entered in any order. They are:
Report Types:
DIF
Display differential information for the all elements
R
Displays raw (unfiltered) analog data and raw station battery
Displays preceding 1.5 cycles (including reports with ‘L’ options)
Allows S4, S8, S16, S32, and S64
Defaults
to
S16
samples/cycle
(
default
)
Display cosine filtered fundamental currents on all windings and
station battery averaged for 1 cycle
Report
Options:
n
Event number
Default
to
1
Sx
Samples per cycle
x = 4 or 8 (See ‘R’ option)
Default to 4 if Sx not specified
Ly
Display first y cycles of event report
y = 1 - LER
Default to L15 if Ly not specified
Ly-
Displays event report from cycle y to end of report
Ly-w
Displays event report from cycle y to cycle w
C
Default to 8 samples/cycle (same as EVE C)
Note
: If Sx and/or Ly are given, they override all other parameters.
Note
:
The L and U parameters are supported for consistency with the SEL-321 Relay.