E-4
Compressed ASCII Commands
Date Code 20010521
SEL-387E Instruction Manual
"16H","IAW1","IBW1","ICW1","IAW2","IBW2","ICW2","IAW3","IBW3","ICW3","VAWX",
"VBWX","VCWX","VDC","FREQ","TRIG","
NAMES OF ELEMENTS IN ALL RELAY
WORD ROWS
"," yyyy"<CR>
"1056D","F","F","F","F","F","F","F","F","F","F","F","F","F","F","1S","88S"," yyyy"<CR>
"
CTA
",1," yyyy"<CR>
"8h","6S","6S","6S","6S","6S","6S","6S","6S"," yyyy"<CR>
"1D","I","I","I","I","I","I","I","I"," yyyy"<CR>
<ETX>
where
yyyy is the 4-byte ASCII representation of the hex checksum for the line.
#H identifies a header line to precede one or more data lines, ‘#’ is the number of
subsequent ASCII names. For example, "21H" identifies a header line with 21 ASCII
labels.
#h identifies a header line to precede one or more data lines, ‘#’ is the number of
subsequent format fields. For example, "8h" identifies a header line with 8 format
fields.
#D identifies a data format line, ‘#’ is the maximum number of subsequent data lines,
each format field contains one of the following type designators:
I
Integer
data
F
Floating point data
mS
String of max ‘m’ characters (e.g., 10S for a 10 char string)
If a Compressed ASCII request is made for data that are not available, (e.g., the history buffer is
empty or invalid event request), the relay responds with the following message:
<STX>"No Data Available","0668"<CR><ETX>
Note:
If the analog current input names (IAW1, etc.) have been changed via the Analog Input
Labels global settings, they will appear in the above report as set.
CBREAKER C
OMMAND
Display the SEL-387E Relay Compressed ASCII breaker report by sending:
CBR <ENTER>
The relay sends:
<STX>
"FID","yyyy"<CR>
"FID=SEL-387E-XXXX-V-ZXXXXXX-DXXXXXXXX","yyyy"<CR>
"MONTH_","DAY_","YEAR_","HOUR_","MIN_","SEC_","MSEC_","yyyy"<CR>
xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,xxxx,"yyyy"<CR>
"BREAKER","INT_TRIPS","IAW","IBW","ICW","EXT_TRIPS","IAW","IBW","ICW",
"POLE1","POLE2","POLE3","MONTH","DAY","YEAR","HOUR","MIN","SEC","MSEC","yy
yy"<CR>