A-2
Firmware Versions
Date Code 20020218
SEL-387 Instruction Manual
Firmware
Part/Revision No.
Description of Firmware
-
Changed !ALARM Relay Word bit to
NOTALM.
-
Corrected ADC power up.
-
Corrected minimum pickup using 24IP
setting in Volts/Hertz user-defined curve.
SEL-387E-R205-V0-Z101101-D20020214
SEL-387E-R104-V0-Z001001-D20020214
Supports PROTO=DNP protocol setting
option.
Does not support POTO=DNP protocol setting
option.
This firmware differs from the previous
version as follows:
-
Corrected minimum pickup using 24IP
setting in Volts/Hertz user-defined curve.
SEL-387E-R204-V0-Z101101-D20010906
SEL-387E-R103-V0-Z001001-D20010906
Supports PROTO=DNP protocol setting
option.
Does not support POTO=DNP protocol setting
option.
This firmware differs from the previous
version as follows:
-
Removed 32IOP as input to “REF
Directional Element” logic AND gate. With
32IOP removed as an input, the AND gate
only uses 32IE and 50GC as inputs. Changed
50GP multiplier from 0.9 to 0.8 in 50GC logic.
This change only affects R103 (without DNP)
since R203 (with DNP) already incorporated
the change.
-
Corrected front-panel PWR meter display
to properly scroll to the bottom of the list of
power quantities when the up arrow is used
and VIWDG is set to either 1 or 2.
-
Corrected front-panel METER display to
support PWR when TPVI=N, WnCT=D, and
VIWDG=N.
SEL-387E-R203-V0-Z101101-D20010102
Supports the PROTO=DNP protocol setting
option.
This firmware differs from the previous
version as follows:
-
Included W1, W2 combination in