8
SEL-387E Relay Command Summary
Date Code 20020129
SEL-387E Instruction Manual
SER d1
Show rows in the Sequential Events Recorder (SER) event report for date d1.
SER d1 d2
Show rows in the Sequential Events Recorder (SER) event report from date d1 to d2.
Entry of dates is dependent on the Date Format setting DATE_F (= MDY or YMD).
SER C
Clear the Sequential Events Recorder (SER) event reports from memory.
SET n
Change relay group settings (overcurrent, differential, etc.).
For the SET commands, parameter n is the setting name at which to begin editing
settings. If parameter n is not entered, setting editing starts at the first setting.
SET G
Change global settings.
SET P n
Change port settings.
SET R
Change Sequential Events Recorder (SER) settings.
SHO n
Show relay group n settings. Shows active group if n is not specified.
SHO G
Show relay global settings.
SHO P
Show port settings and identification of port to which user is connected.
SHO P n
Show port settings for Port n (n =1, 2, 3, 4).
SHO R
Show Sequential Events Recorder (SER) settings.
STA
Show relay self-test status.
TAR R
Return front-panel LED targets to regular operation and reset the tripping front-panel
targets.
TAR n k
Show Relay Word row n status (n = 0 through 41). Enter number k to scroll Relay
Word row n status k times on screen.
Append F to display targets on the front panel, second row of LEDs.
TIM
Show or set time (24-hour time). Show time presently in the relay by entering just
TIM. Example time 22:47:36 is entered with command TIM 22:47:36.
TRI
Trigger an event report.