SEL-387E Settings Sheets
Page 11 of 27
Group Settings (SET Command)
Date
Group
Date Code 20020129
Level 1 Time Delay (0.04–400.00 seconds)
24D1D
=
Level 2 Composite Curve Shape (OFF, DD, ID, I, U)
24CCS
=
Level 2 Inv.-Time Pickup (100–200%) 24IP
=
Level 2 Inv.-Time Curve (0.5, 1.0, 2.0)
24IC
=
Level 2 Inv.-Time Factor (0.1–10.0 seconds)
24ITD
=
Level 2 Pickup One (100–200%) 24D2P1
=
Level 2 Time Delay One (0.04–400.00 seconds)
24D2D1
=
Level 2 Pickup Two (101–200%) 24D2P2
=
Level 2 Time Delay Two (0.04–400.00 seconds)
24D2D2
=
Level 2 Reset Time (0.00–400.00 seconds)
24CR
=
24 Element Torque-Control (SEL
OGIC
control equation)
24TC =
27 E
LEMENTS
Level 1 Phase U/V PU (OFF, 0.1–300.0 V secondary)
27P1P
=
Level 2 Phase U/V PU (OFF, 0.1–300.0 V secondary)
27P2P
=
Level 1 Phase-Phase U/V PU (OFF, 0.1–520.0 V secondary)
27PP1
=
Level 2 Phase-Phase U/V PU (OFF, 0.1–520.0 V secondary)
27PP2
=
Pos.-Seq. U/V PU (OFF, 0.1–100.0 V secondary)
27V1P
=
59 E
LEMENTS
Level 1 Phase O/V PU (OFF, 0.0–300.0 V secondary)
59P1P
=
Level 2 Phase O/V PU (OFF, 0.0–300.0 V secondary)
59P2P
=
Level 1 Residual O/V PU (OFF, 0.0–300.0 V secondary)
59G1P
=
Level 2 Residual O/V PU (OFF, 0.0–300.0 V secondary)
59G2P
=
Neg.-Seq. U/V PU (OFF, 0.0–100.0 V secondary)
59QP
=
Level 1 Phase-Phase O/V PU (OFF, 0.0–520.0 V secondary)
59PP1
=
Level 2 Phase-Phase O/V PU (OFF, 0.0–520.0 V secondary)
59PP2
=
Pos.-Seq.(V1) O/V PU (OFF, 0.0–100.0 V secondary)
59V1P
=
81 E
LEMENTS
Undervoltage Block (20.0–150.0 V secondary)
27B81P
=
Level 1 Pickup (OFF, 40.10–65.00 Hz)
81D1P
=
Level 1 Time Delay (0.04–300.00 seconds)
81D1D
=
Level 2 Pickup (OFF, 40.10–65.00 Hz)
81D2P
=