Group Settings (SET Command)
Date
Group
Date Code 20020129
51Q2 Torque Control (SEL
OGIC
control equation)
51Q2TC =
W
INDING
2 R
ESIDUAL
O/C E
LEMENTS
Residual Def.-Time O/C Level 1 PU
(OFF,
0.25–100.00 A secondary) (5 A)
(OFF,
0.05–20.00 A secondary) (1 A)
50N21P
=
Residual Level 1 O/C Delay (0–16000 cycles)
50N21D
=
50N21 Torque Control (SEL
OGIC
control equation)
50N21TC =
Residual Inst. O/C Level 2 PU
(OFF,
0.25–100.00 A secondary) (5 A)
(OFF,
0.05–20.00 A secondary) (1 A)
50N22P
=
50N22 Torque Control (SEL
OGIC
control equation)
50N22TC =
Residual Inv.-Time O/C PU
(OFF,
0.5–16.0 A secondary) (5 A)
(OFF,
0.1–3.2 A secondary) (1 A)
51N2P
=
Residual Inv.-Time O/C Curve (U1–U5, C1–C5) 51N2C
=
Residual Inv.-Time O/C Time-Dial (US 0.5–15.0, IEC 0.05–1.00) 51N2TD
=
Residual Inv.-Time O/C EM Reset (Y, N)
51N2RS
=
51N2 Torque Control (SEL
OGIC
control equation)
51N2TC =
W
INDING
2 D
EMAND
M
ETERING
Demand Ammeter Time Constant (OFF, 5–255 min)
DATC2
=
Phase Demand Ammeter Threshold
(0.5–16.0 A secondary) (5 A)
(0.1–3.2 A secondary) (1 A)
PDEM2P =
Neg.-Seq. Demand Ammeter Threshold
(0.5–16.0 A secondary) (5 A)
(0.1–3.2 A secondary) (1 A)
QDEM2P =
Residual Demand Ammeter Threshold
(0.5–16.0 A secondary) (5 A)
(0.1–3.2 A secondary) (1 A)
NDEM2P =