SEL-387E Settings Sheets
Page 5 of 27
Group Settings (SET Command)
Date
Group
Date Code 20020129
Residual Inv.-Time O/C PU
(OFF,
0.5–16.0 A secondary) (5 A)
(OFF,
0.1–3.2 A secondary) (1 A)
51N1P
=
Residual Inv.-Time O/C Curve (U1–U5, C1–C5) 51N1C
=
Residual Inv.-Time O/C Time-Dial (US 0.5–15.0, IEC 0.05–1.00) 51N1TD
=
Residual Inv.-Time O/C EM Reset (Y, N)
51N1RS
=
51N1 Torque Control (SEL
OGIC
control equation)
51N1TC =
W
INDING
1 D
EMAND
M
ETERING
Demand Ammeter Time Constant (OFF, 5–255 min)
DATC1
=
Phase Demand Ammeter Threshold
(0.5–16.0 A secondary) (5 A)
(0.1–3.2 A secondary) (1 A)
PDEM1P =
Neg.-Seq. Demand Ammeter Threshold
(0.5–16.0 A secondary) (5 A)
(0.1–3.2 A secondary) (1 A)
QDEM1P =
Residual Demand Ammeter Threshold
(0.5–16.0 A secondary) (5 A)
(0.1–3.2 A secondary) (1 A)
NDEM1P =
W
INDING
2 O/C E
LEMENTS
W
INDING
2 P
HASE
O/C E
LEMENTS
Phase Def.-Time O/C Level 1 PU
(OFF,
0.25–100.00 A secondary) (5 A)
(OFF,
0.05–20.00 A secondary) (1 A)
50P21P
=
Phase Level 1 O/C Delay (0–16000 cycles)
50P21D
=
50P21 Torque Control (SEL
OGIC
control equation)
50P21TC =
Phase Inst. O/C Level 2 PU
(OFF,
0.25–100.00 A secondary) (5 A)
(OFF,
0.05–20.00 A secondary) (1 A)
50P22P
=
50P22 Torque Control (SEL
OGIC
control equation)
50P22TC =