SEL-387E Settings Sheets
Page 4 of 27
Group Settings (SET Command)
Date
Group
Date Code 20020129
W
INDING
1 N
EGATIVE
-S
EQUENCE
O/C E
LEMENTS
Note: All negative-sequence element pickup settings are in terms of 3I
2
.
Neg.-Seq. Def.-Time O/C Level 1 PU
(OFF,
0.25–100.00 A secondary) (5 A)
(OFF,
0.05–20.00 A secondary) (1 A)
50Q11P
=
Neg.-Seq. Level 1 O/C Delay (0.5–16000 cycles)
50Q11D
=
50Q11 Torque Control (SEL
OGIC
control equation)
50Q11TC =
Neg.-Seq. Inst. O/C Level 2 PU
(OFF,
0.25–100.00 A secondary) (5 A)
(OFF,
0.05–20.00 A secondary) (1 A)
50Q12P
=
50Q12 Torque Control (SEL
OGIC
control equation)
50Q12TC =
Neg.-Seq. Inv.-Time O/C PU
(OFF,
0.5–16.0 A secondary) (5 A)
(OFF,
0.1–3.2 A secondary) (1 A)
51Q1P
=
Neg.-Seq. Inv.-Time O/C Curve (U1–U5, C1–C5) 51Q1C
=
Neg.-Seq. Inv.-Time O/C Time-Dial (US 0.5–15.0, IEC 0.05–1.00) 51Q1TD
=
Neg.-Seq. Inv.-Time O/C EM Reset (Y, N)
51Q1RS
=
51Q1 Torque Control (SEL
OGIC
control equation)
51Q1TC =
W
INDING
1 R
ESIDUAL
O/C E
LEMENTS
Residual Def.-Time O/C Level 1 PU
(OFF,
0.25–100.00 A secondary) (5 A)
(OFF,
0.05–20.00 A secondary) (1 A)
50N11P
=
Residual Level 1 O/C Delay (0–16000 cycles)
50N11D
=
50N11 Torque Control (SEL
OGIC
control equation)
50N11TC =
Residual Inst. O/C Level 2 PU
(OFF,
0.25–100.00 A secondary) (5 A)
(OFF,
0.05–20.00 A secondary) (1 A)
50N12P
=
50N12 Torque Control (SEL
OGIC
control equation)
50N12TC =