6-12
Setting the Relay
Date Code 20020129
SEL-387E Instruction Manual
SEL-387E Relay Default Settings (5 A)
=>>SHO<ENTER>
Group 1
RID =XFMR 1
TID =STATION A
E87W1 = Y E87W2 = Y E87W3 = Y
EOC1 = Y EOC2 = Y EOC3 = Y EOCC = N
E24 = Y E27 = Y E59 = Y
E81 = N
ESLS1 = N ESLS2 = N ESLS3 = N
W1CT = Y W2CT = Y W3CT = Y
CTR1 = 120 CTR2 = 240 CTR3 = 400
MVA = 100.0 ICOM = Y
W1CTC = 11 W2CTC = 11 W3CTC = 0
VWDG1 = 230.00 VWDG2 = 138.00 VWDG3 = 13.80
PTR = 2000 COMPANG = 0 VIWDG = 1 TPVI = Y
TAP1 = 2.09 TAP2 = 1.74 TAP3 = 10.46
O87P = 0.3 SLP1 = 25 SLP2 = 50 IRS1 = 3.0
U87P = 10.0 PCT2 = 15 PCT5 = 35
TH5P = OFF IHBL = N
E32I =0
50P11P = 20.00 50P11D = 5.00 50P11TC =1
50P12P = OFF
50P13P = 0.50 50P14P = 4.00
51P1P = 4.00 51P1C = U2 51P1TD = 3.00 51P1RS = Y
51P1TC =1
50Q11P = OFF 50Q12P = OFF
51Q1P = 6.00 51Q1C = U2 51Q1TD = 3.00 51Q1RS = Y
51Q1TC =1
50N11P = OFF 50N12P = OFF
51N1P = OFF
DATC1 = 15 PDEM1P = 7.00 QDEM1P = 1.00 NDEM1P = 1.00
50P21P = OFF 50P22P = OFF
50P23P = 0.50 50P24P = 3.50
51P2P = 3.50 51P2C = U2 51P2TD = 3.50 51P2RS = Y
51P2TC =1
50Q21P = OFF 50Q22P = OFF
51Q2P = 5.25 51Q2C = U2 51Q2TD = 3.50 51Q2RS = Y
51Q2TC =1
50N21P = OFF 50N22P = OFF
51N2P = OFF
DATC2 = 15 PDEM2P = 7.00 QDEM2P = 1.00 NDEM2P = 1.00
50P31P = 7.00 50P31D = 0.00 50P31TC =1
50P32P = OFF
50P33P = 0.50 50P34P = 4.00
51P3P = 4.00 51P3C = U2 51P3TD = 1.30 51P3RS = Y
51P3TC =1
50Q31P = OFF 50Q32P = OFF
51Q3P = OFF
50N31P = OFF 50N32P = OFF
51N3P = OFF
DATC3 = 15 PDEM3P = 7.00 QDEM3P = 1.00 NDEM3P = 1.00