8-26
Breaker/Recloser Monitor, Battery System Monitor,
Date Code 20020215
Metering, and Load Profile Functions
SEL-351R Instruction Manual
Time = 10 Minutes
The three 5-minute intervals in the sliding time-window at “Time = 10 minutes” each integrate
into the following 5-minute totals:
5-Minute Totals
Corresponding
5-Minute Interval
0.0 per unit
–5 to 0 minutes
1.0 per unit
0 to 5 minutes
1.0 per unit
5 to 10 minutes
2.0 per unit
Rolling demand meter response at “Time = 10 minutes” = 2.0/3 = 0.67 per unit
Time = 15 Minutes
The three 5-minute intervals in the sliding time-window at “Time = 15 minutes” each integrate
into the following 5-minute totals:
5-Minute Totals
Corresponding
5-Minute Interval
1.0 per unit
0 to 5 minutes
1.0 per unit
5 to 10 minutes
1.0 per unit
10 to 15 minutes
3.0 per unit
Rolling demand meter response at “Time = 15 minutes” = 3.0/3 = 1.0 per unit
Demand Meter Settings
Table 8.5: Demand Meter Settings and Settings Range
Setting Definition
Range
EDEM
Demand meter type
THM = thermal
ROL = rolling
DMTC
Demand meter time constant
5, 10, 15, 30, or 60 minutes
PDEMP
Phase demand current pickup
OFF
NDEMP*
Neutral ground demand current pickup
0.10–3.20 A (1 A nominal)
GDEMP
Residual ground demand current pickup
in 0.01 A steps
QDEMP
Negative-sequence demand current pickup
*0.005–0.160A (0.05 A nominal channel IN current input)
Note
: Changing setting EDEM or DMTC resets the demand meter values to zero. This also
applies to changing the active setting group, and setting EDEM or DMTC is different in
Summary of Contents for SEL-351R
Page 12: ......
Page 14: ......
Page 18: ......
Page 74: ......
Page 76: ......
Page 82: ......
Page 136: ......
Page 140: ......
Page 176: ......
Page 180: ......
Page 332: ......
Page 334: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 478: ......
Page 510: ......
Page 512: ......
Page 522: ......
Page 548: ......
Page 550: ......
Page 576: ......
Page 610: ......
Page 616: ......