6-18
Close and Reclose Logic
Date Code 20020215
SEL-351R Instruction Manual
Table 6.3: Shot Counter Correspondence to Relay Word Bits and Open Interval Times
Shot
Corresponding
Relay Word Bit
Corresponding
Open Interval
0 SH0
79OI1
1 SH1
79OI2
2 SH2
79OI3
3 SH3
79OI4
4 SH4
When the shot counter is at a particular shot value (e.g., shot = 2), the corresponding Relay
Word bit asserts to logical 1 (e.g., SH2 = logical 1).
The shot counter also increments for sequence coordination operation. The shot counter can
increment beyond the last shot for sequence coordination [see
Sequence Coordination Setting
Reclosing Relay SEL
OGIC
Control Equation Settings Overview
Table 6.4: Reclosing Relay SEL
OGIC
Control Equation Settings
SEL
OGIC
Control
Equation Setting
Factory Setting
Definition
79RI TRIP
Reclose
Initiate
79RIS
52A + 79CY
Reclose Initiate Supervision
79DTL
67N3T * OLS + (67P1 + 67G1 +
67N1) * TRIP + (!LT2 + !LT7)
* (TRIP + !52A) + 81D1T + PB9
+ OC + SV16
Drive-to-Lockout
79DLS 79LO
Drive-to-Last
Shot
79SKP 0
Skip
Shot
79STL
TRIP
Stall Open Interval Timing
79BRS
51P1 + 51P2 + 51G1 + 51G2 +
51N1 + 51N2 + 67N3 + TRIP
Block Reset Timing
79SEQ
79RS * (51P1 + 51G1 + 51N1)
* SEQC
Sequence Coordination
79CLS
59A1 * !NOBATT * BCBOK *
!DTFAIL
Reclose Supervision
These settings are discussed in detail in the remainder of this subsection.
The longer factory settings are explained in
Section 1: Factory-Set Logic
.
Summary of Contents for SEL-351R
Page 12: ......
Page 14: ......
Page 18: ......
Page 74: ......
Page 76: ......
Page 82: ......
Page 136: ......
Page 140: ......
Page 176: ......
Page 180: ......
Page 332: ......
Page 334: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 478: ......
Page 510: ......
Page 512: ......
Page 522: ......
Page 548: ......
Page 550: ......
Page 576: ......
Page 610: ......
Page 616: ......