4.38
SEL-351A Relay
Instruction Manual
Date Code 20080213
Loss-of-Potential, Load Encroachment, and Directional Element Logic
Directional Control Settings (Not in SEL-351A-1)
Directional Control Settings (Not in SEL-351A-1)
The directional control for overcurrent elements is enabled by making
directional control enable setting E32. Setting E32 has setting choices:
➤
Y enable directional control
➤
N disable directional control
➤
AUTO enable directional control and set many of the
directional element settings automatically
If directional control enable setting E32 = N, directional control is disabled
and no directional control settings are made. All level direction settings are set
internally as:
DIR1 = N (no directional control for Level 1 overcurrent elements)
DIR2 = N (no directional control for Level 2 overcurrent elements)
DIR3 = N (no directional control for Level 3 overcurrent elements)
DIR4 = N (no directional control for Level 4 overcurrent elements)
With the above settings, the directional control outputs in
,
assert to logical 1. The overcurrent
elements referenced in
,
,
, and
are then not controlled by the directional control logic.
There is one case that does not allow group setting E32 = Y or AUTO. If all
three of the following are true, E32 can only be set to “N.”
➤
The relay model has a 0.2 A or 0.05 A nominal neutral channel
➤
Global setting VSCONN = VS
➤
Group setting VNOM = OFF
Settings Made
Automatically
If the directional control enable setting E32 is set:
E32 =
AUTO
then the following directional control settings are calculated and set
automatically:
Z2F, Z2R, 50QFP, 50QRP, a2, k2, 50GFP, 50GRP, a0, Z0F, Z0R, and
Z0MTA
If E32 = AUTO, then Z0MTA is set equal to Z0ANG and Z0MTA is hidden.
Once these settings are calculated automatically, they can only be modified if
the user goes back and changes the directional control enable setting to E32 =
Y.
The remaining directional control settings are
not
set automatically if setting
E32 = AUTO. They have to be set by the user, whether setting E32 = AUTO or
Y. These settings are:
DIR1, DIR2, DIR3, DIR4, ORDER, 50P32P, 50NFP, 50NRP, a0N,
59RES, 32WFP, 32WRP, 32WD, and E32IV (E32IV is a SEL
OGIC
setting)
All these settings are explained in detail in the remainder of this subsection.
Summary of Contents for SEL-351A
Page 10: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 16: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 34: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 126: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 184: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 198: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 228: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 278: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 384: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 410: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 450: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 454: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 472: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 504: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 558: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 562: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 586: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 608: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 666: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...